| Plan Review Notes For Permit 23020774 |
| Permit Number |
23020774 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-22 09:31:03 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #23020774 | | | 294 GRANADA RD | | | | | | PREVIOUS COMMENT: | | | 1- GENERATOR CONCRETE PAD ENGINEERING HAS A COPY OF THE | | | ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL | | | SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. | | | ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL | | | SIGNATURE. | | | | | | RESPONSE: | | | REVISED CONCRETE PAD ENGINEERING UPLOADED TO PROJECTDOX | | | ON 3/20/23 DOESN'T HAVE A DIGITAL SIGNATURE. IT SHOWS | | | AS COPY OF THE DIGITAL SIGNATURE. NEED ORIGINAL | | | VERIFIABLE DIGITAL SIGNATURE. | | | | | | 2- OK. | | | | | | NEW COMMENT: | | | 3. GENERATOR SPECS WERE REMOVED WHEN UPLOADING THE | | | CONCRETE PAD ENGINEERING. ONLY THE CONCRETE PAD | | | ENGINEERING WAS UPLOADED ON 3/20/23. NEED TO PROVIDE | | | THE GENERATOR SPECS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|