 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE INDICATE WITHIN THE NOA
 (#20-0723.29) THE SYSTEM THAT WILL BE USED. THE SYSTEM
 THAT APPEARS TO HAVE BEEN SELECTED DOES NOT APPEAR TO
 MEET THE WINDLOAD PRESSURE REQUIREMENTS. PLEASE REVIEW,
 EVALUATE, & SELECT THE DIFFERENT SYSTEMS THAT WILL MEET
 THE WINDLOAD PRESSURE REQUIREMENTS FOR ALL ROOF ZONES
 SUCH AS SYSTEM # E-24.