| 2023-07-06 17:11:37 | RESIDENTIAL(R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020716 |
| | 2735 EMBASSY DR. |
| | |
| | PROVISO NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR |
| | PRODUCT APPROVALS/ DEFERRED SUBMITTAL). |
| | |
| | ***IMPORTANT*** |
| | BUILDING REVIEW WILL BE APPROVED WITH PROVISO ONCE THE |
| | ENERGY CALCULATIONS ARE CERTIFIED AT THE BOTTOM OF FORM |
| | BY THE OWNER OR AUTHORIZED AGENT AND THE ENGINEER |
| | ADDRESSES THE DIGITAL SIGNATURE REVIEW COMMENTS. |
| | |
| | ***IMPORTANT |
| | ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED |
| | AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | 1- LOT DRAINAGE. PROPOSED WORK AFFECTS THE LOT |
| | DRAINAGE. PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE |
| | DRAINAGE IS KEPT WITHIN THE LOT AND NOT DIVERTED TO |
| | ADJACENT PROPERTIES. PROVIDE DRAINAGE PLAN SHOWING |
| | COMPLIANCE WITH THE FOLLOWING SECTIONS: R401.3 |
| | FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS AND SEC. |
| | 110.9 CITY AMENDMENTS. |
| | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| | ADJACENT PROPERTIES. |
| | |
| | RESPONSE: |
| | 1- SITE DRAINAGE PLANS HAVE AN ENGINEER'S |
| | SELF-CERTIFIED DIGITAL SIGNATURE. ENGINEER CANNOT |
| | SELF-CERTIFY THE DIGITAL SIGNATURE. THIRD PARTY |
| | CERTIFICATION IS REQUIRED BY FAC 61G15-23.004. (NOTE: |
| | ENGINEER TO CONTACT THE BOARD OF ENGINEER'S FOR |
| | SELF-CERTIFIED DIGITAL SIGNATURE QUESTIONS). |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | STAIRWAY CONSTRUCTION: DIMENSIONS, RISERS, TREADS, |
| | NOSING, HANDRAILS, GUARDRAILS, ETC. SHOWING COMPLIANCE |
| | WITH SEC. R311.7 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | EVEN THOUGH THIS WILL BE DEFERRED SUBMITTAL, THE |
| | DESIGNER OF RECORD STILL NEEDS TO SPECIFY THE DESIGN |
| | GUIDELINES REQUIRED BY TABLE R301.5, SEC. R311.7. AND |
| | SEC. R312.1 FBC-RESIDENTIAL. NOTE: JUST CITING THE CODE |
| | SECTION IS NOT ALLOWED (SEC. 107.2.1 CITY AMENDMENTS). |
| | CLEARLY SPECIFY ON PLANS THE DESIGN GUIDELINES AND |
| | STATE ON DRAWINGS THAT SHOP DRAWINGS NEED TO BE |
| | SUBMITTED FOR DESIGNER OF RECORD REVIEW. ALL SHOP |
| | DRAWINGS TO BE REVIEWED BY THE DESIGN PROFESSIONAL OF |
| | RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | NOTE: OPEN RISERS NEED TO MEET THE REQUIREMENTS OF SEC. |
| | R311.7.5.1 FBC-RESIDENTIAL. |
| | |
| | 5- LIVING AREA SLIDING GLASS DOORS. BASED ON PLANS AND |
| | DOOR SCHEDULE, IT LOOKS LIKE THERE ARE TWO SLIDING |
| | GLASS DOORS MULLED TOGETHER. SPECIFY MULLION SIZE AND |
| | CONNECTIONS AND PROVIDE PRODUCT APPROVAL.. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | EVEN THOUGH THIS WILL BE DEFERRED SUBMITTAL, THE |
| | DESIGNER OF RECORD STILL NEEDS TO SPECIFY THE MULLION |
| | TYPE, SIZE AND CONNECTORS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 8- BALCONY GUARDRAIL: IT IS NOT CLEAR WHAT TYPE OF |
| | RAILING IS GOING TO BE INSTALLED. SECOND FLOOR PLANS |
| | SPECIFIES 36" HIGH RAILING W/ PICKETS TO REJECT A 4" |
| | DIAM. SPHERE, WHILE REAR ELEVATION SHOWS GUARDRAIL THAT |
| | LOOKS LIKE A CABLE SYSTEM. REVISE AS REQUIRED TO MATCH |
| | AND PROVIDE THE DETAILS AND SPECIFICATIONS FOR THE |
| | CONSTRUCTION OF THE GUARDRAIL SHOWING COMPLIANCE WITH |
| | TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT |
| | DESIGN DETAILS AND SPECIFICATIONS ARE MET. |
| | |
| | RESPONSE: |
| | EVEN THOUGH THIS WILL BE DEFERRED SUBMITTAL, THE |
| | DESIGNER OF RECORD STILL NEEDS TO SPECIFY THE DESIGN |
| | GUIDELINES REQUIRED BY TABLE R301.5, SEC. R311.7. AND |
| | SEC. R312.1 FBC-RESIDENTIAL. |
| | |
| | 11-PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE |
| | SHUTTERS CONSTRUCTION AND INSTALLATION. SPECIFY |
| | FASTENING. SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | WILL BE A DEFERRED SUBMITTAL. |
| | |
| | 18- PRODUCT APPROVALS DEFERRED SUBMITTAL AFTER PERMIT |
| | IS ISSUED(APPROVED BY ENGINEER OF RECORD): |
| | A)ALL EXTERIOR DOORS. |
| | B)ALL WINDOWS. |
| | C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE). |
| | D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. |
| | E)METAL ROOF (IF USED). |
| | F)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED. |
| | G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| | H)ROOF TILE ADHESIVE(IF USED)LISTED IN ROOF TILE |
| | PRODUCT APPROVAL. |
| | I)HIP & RIDGE METAL SUPPORT TO BE USED. |
| | J)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE |
| | TILE. |
| | K) FLAT ROOF. AND, CLEARLY MARK ASSEMBLY TO BE |
| | INSTALLED. |
| | |
| | 20- ENERGY CALCULATIONS: |
| | A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM |
| | THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS |
| | PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO |
| | RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER NAME, BUILDER NAME (IF AVAILABLE), |
| | CORRECT PERMIT OFFICE (CITY OF WEST PALM BEACH NOT PALM |
| | BEACH COUNTY), JURISDICTION NUMBER (THIS JURISDICTION |
| | IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | OWNER'S NAME IS INCORRECT, BUILDER'S NAME IS INCORRECT. |
| | REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS |
| | AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. PROVIDE NAME , NOT SIGNATURE. |
| | |
| | G)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |