| Plan Review Notes For Permit 23020702 |
| Permit Number |
23020702 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-27 13:45:42 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23020702 | | | 3/27/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS PL-1, PL-2 & PL-3: THE PLANS HAVE CONFLICTING | | | INFORMATION PER THE ITEMS LISTED BELOW- SEC. 107.2.1 | | | WPB. | | | | | | A) PL-1 & PL-2 SPECIFY A 10,000 GALLON POOL HOWEVER THE | | | FLOW RATE AND TDH CALCULATIONS ON PL-3 ARE BASED ON | | | 4,680 GALLONS. | | | | | | B) PL-2 & PL-3: THE POOL PIPING DIAGRAM ON PL-2 DOES | | | NOT MATCH THE POOL PIPING SCHEMATIC ON PL-3. IT APPEARS | | | THE DIAGRAM IS A COPY AND PASTE DETAIL. PLEASE REVISE | | | IT OR REMOVE IT. | | | | | | C) PL-2 & PL-3: A 2HP SPA PUMP IS SPECIFIED ON PL-2. | | | A1.65 HP SPA AND POOL PUMP IS SPECIFIED ON P-3. | | | | | | D) PL-1, PL-2 & PL-3: A CHANNEL DRAIN IS SHOWN IN THE | | | SPA ON PL-1 & PL-2, HOWEVER THE PL-3 PIPING SCHEMATIC | | | SHOWS TWO INDIVIDUAL ROUND DRAINS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|