| Date |
Text |
| 2023-04-24 15:43:05 | RESIDENTIAL(R2) THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020661 |
| | 1006 10TH ST |
| | |
| | 1- FLOORING SOUND INSULATION MATERIAL: |
| | |
| | ORIGINAL COMMENT: |
| | (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| | (2020). |
| | |
| | RESPONSE: |
| | INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA |
| | SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS |
| | WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST |
| | REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE |
| | USED. |
| | |
| | ORIGINAL COMMENT: |
| | (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | RESPONSE: |
| | INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA |
| | SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS |
| | WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST |
| | REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE |
| | USED. |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| | ( WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| | FLOOR FINISH. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | RESPONSE: |
| | INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA |
| | SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS |
| | WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST |
| | REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE |
| | USED. |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| | ( WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| | FLOOR FINISH. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |