| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL1654-R31 HAS NOT BEEN |
| | APPROVED YET; FL1654-R30 IS THE CURRENT APPROVED |
| | VERSION. PLEASE PROVIDE THE FOLLOWING: INCLUDE COVER |
| | PAGE, EVALUATION REPORT PAGES 1-5 AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR PRODUCT |
| | APPROVAL FL1654-R31 SYSTEM NO. W-194 DO NOT MEET THE |
| | MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| | FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| | MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| | EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| | ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| | SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | AS PER RULE 61G20-3. |
| | 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL34539 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL |
| | INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS |
| | WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER, |
| | STATUS, GENERAL INFORMATION ABOUT THE PRODUCT). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |