2023-03-13 13:29:29RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020586
 935 CHARLES ST
  
 1- THIS BUILDING IS GOING TO BE BUILT IN A AE FLOOD
 ZONE WITH THE BASE FLOOD BFE:12.1 FEET BASED ON NAVD
 1988. CITY OF WEST PALM BEACH ORDINANCE REQUIRES A TWO
 (2) FOOT FREE BOARD ABOVE THE BASE FLOOD ELEVATION
 (SEC. 18-284 CITY ORDINANCE NO. 4729-17). THEREFORE,
 THE REQUIRED FINISH FLOOR ELEVATION IS 14.1 FEET MIN.
 NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY THE PROPOSED
 FINISHED ELEVATION IN ALL ROOMS IN ALL FLOOR PLANS.
 ALSO, DESIGNER OF RECORD NEEDS TO SPECIFY THE FINISH
 ELEVATION ALL THE EQUIPMENT SERVING THE BUILDING. SEE
 SURVEY FOR EXISTING GRADE ELEVATIONS.
  
 DURING THE PERMITTING/CONSTRUCTION OF THIS STRUCTURE
 THREE DIFFERENT FLOOD ELEVATION CERTIFICATES WILL BE
 REQUIRED (SEC. 107.3.5.1.1 CITY AMENDMENTS):
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 NOTE:
 NEED TO PROVIDE THE CONSTRUCTION DRAWINGS ELEVATION
 CERTIFICATE NOW FOR REVIEW.
  
 2- PROVIDE DRAINAGE PLAN SHOWING EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES. PROVIDE SURVEY SHOWING GRADE
 ELEVATIONS AND PROPOSED BUILDING.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY THE
 OWNER/AGENT AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 4- NEED INFORMATION TO SHOW COMPLIANCE WITH BEDROOM #2
 EGRESS WINDOW.
 CLEARLY SPECIFY SIZE OF CASEMENT WINDOW AND PROVIDE
 MANUFACTURER'S SPECS SHOWING THAT SPECIFIED SIZE MEETS
 ALL THE EGRESS REQUIREMENTS.
 NOTE: COORDINATE WITH SIZE OF WINDOW OPENINGS SHOWN ON
 THE SECOND FLOOR PLAN.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 5- BASED ON TABLE R301.2(2) FBC-RESIDENTIAL AND HEIGHT
 AND EXPOSURE ADJUSTMENT TABLE R301.2(3) FBC-RESIDENTIAL
 THE DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET
 A-2 AND A-4 ARE TOO LOW. REVISE DESIGN PRESSURES AS
 REQUIRED BASED ON OPENING ZONE LOCATION (4 OR 5) AND
 BUILDING MEAN ROOF HEIGHT. (I USED 30 FEET MEAN ROOF
 HEIGHT FROM THE TABLE FOR REFERENCE). REVISE DESIGN
 PRESSURES ON SHEET A-2 AND A-4 AS REQUIRED OR PROVIDE
 ACTUAL CALCULATIONS. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 6- SECOND FLOOR FRAMING PLAN DOESN'T SPECIFY TRUSS SIZE
 AND SPACING. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY TRUSS
 TOP CHORD LIVE AND DEAD LOADS AND BOTTOM CHORD LIVE AND
 DEAD LOADS. R301.1 FBC-RESIDENTIAL.
 NOTE: INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 FBC-RESIDENTIAL.
  
 9- SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 10- SPECIFY ATTIC ACCESS SIZE. SEC. R807.1
 FBC-RESIDENTIAL.
  
 11- GUARDRAILS: DESIGNER OF RECORD TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY GUARDRAILS AS REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 12- STAIR SECTION: PROVIDE DETAILS/SPECIFICATIONS FOR
 STAIRWAY FIREBLOCKING AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 14- ROOFING UNDERLAYMENT: PROVIDE SPECIFICATIONS
 SHOWING HOW COMPLYING WITH THE NEW 2020 CODE
 REQUIREMENT FOR ROOFING UNDERLAYMENT. SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 CLARIFY TYPICAL ROOF NOTE ON SHEET A-4. SPECIFY CORRECT
 ROOFING UNDERLYAMENT BASED ON PROPOSED ROOFING
 MATERIAL.
  
 15- ROOF SHEATHING: PLYWOOD SHEATHING NAILING SCHEDULE:
 REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO COMPLY
 WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. REVISE
 TYPE, SIZE AND SPACING. NOTE: NEED TO USE RING SHANK
 NAILS. ROOF SHEATHING NEEDS TO BE NAILED AT 4 INCHES
 O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: ALSO, REVISE INFORMATION SPECIFIED ON SHEET S-4
 TO MATCH. REVISE DIAPHRAGM SCHEDULE TABLE, FASTENER
 SCHEDULE TABLE AND ROOF SHEATHING DIAGRAM TO MATCH.
 COORDINATE WITH ABOVE REQUIREMENT.
  
 16- PROVIDE DETAIL/SPECS FOR STEEL COLUMNS CONNECTION
 TO TRUSS GIRDER THAT MATCHES PROPOSED INSTALLATION.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 17- PROPOSED ROOF FINISH IS NOT CLEAR. ARCHITECT
 SPECIFIES ROOF TILE BUT PRODUCT APPROVAL SUBMITTED IS
 FOR METAL PANELS. REVISE AS REQUIRED TO MATCH. ALSO,
 ARCHITECT SPECIFIES NON VENTED ATTIC BUT RIDGE VENT
 PRODUCT APPROVAL WAS SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 18- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-20 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 19-PRODUCT APPROVALS. PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR
 LATER AS A DEFERRED SUBMITTAL).
  
 A)ENTRY DOOR.
 B)GARAGE EXTERIOR SWING DOORS.
 C)GARAGE OVERHEAD DOOR. SEE SIZES ON PLANS.
 D)CASEMENT WINDOWS.
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 F)ROOF FINISH. NOTE: COORDINATE WITH ITEM #17 ABOVE.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. COORDINATE
 WITH ITEM #17 ABOVE.
 H)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 I)ROOF VENTS IF SPECIFIED BY THE ARCHITECT. SEE PLANS.
 J)RIDGE ROOF VENT SPECIFIED BY THE ARCHITECT. SEE
 PLANS.
 K) HIP & RIDGE METAL SUPPORT TO BE USED IF TILE
 SPECIFIED ON PLANS.
 L)BALCONY UNDERLAYMENT SPECIFIED ON PLANS.
 M) ROOF TILE (IF SPECIFIED BY ARCHITECT AND CLEARLY
 MARK ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY
 POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC R301.2.1
 FBC-RESIDENTIAL.
  
 20- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: PRODUCT APPROVALS LISTED ON SHEET A-4 DON'T MATCH
 PRODUCT APPROVALS SUBMITTED. REVISE/COORDINATE AS
 REQUIRED TO MATCH PRODUCT APPROVALS SUBMITTED.
  
 21- -STRUCTURAL LEDGER SPECIFICATIONS SHOWN ON THE
 TYPICAL WALL SECTION ON SHEET A-4 AND SPECIFICATIONS
 SHOWN ON THE LEDGER TABLE ON SHEET S-2 DON'T MATCH.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 22- RESIDENTIAL GARAGE FIRE SEPARATION: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR DWELLING-
 GARAGE FIRE SEPARATION AS REQUIRED BY SEC. R302.6
 FBC-RESIDENTIAL AND TABLE R302.6 FBC-RESIDENTIAL.
  
 23- PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE
 SHUTTERS INSTALLATION. SPECIFY FASTENING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 24- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $323936.00. OWES
 $3543.93.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,