| Plan Review Notes For Permit 23020571 |
| Permit Number |
23020571 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-28 13:18:58 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC - R 301.2.1.2 SUBMIT AN INSTALLATION SCHEDULE FOR | | | THE STORM PANELS. SPECIFY THE OPENING SIZE, THE WIND | | | PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING, EDGE | | | DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION DISTANCE | | | FROM PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER | | | FROM THE INSTALLATION PRODUCT APPROVALS. IF YOU NEED A | | | SCHEDULE(FORM), FEEL FREE TO SEND ME A REQUEST BY EMAIL | | | AND I WILL RESPOND WITH AN ATTACHED FROM FOR YOUR | | | CONVENIENCE. | | | |
|