| 2023-03-03 08:15:31 | 1ST REVIEW- FBC FUEL GAS- 2020 |
| | PERMIT- 23020562 |
| | 3/3/23 |
| | |
| | 1) THE LP TANK TIE DOWN DETAIL SHALL BEAR THE DIGITAL |
| | SIGNATURE AND SEAL OF THE ENGINEER OF RECORD- ERIC |
| | SVOBODA IN ACCORDANCE WITH FL. STATUTE 471.025 AND SEC. |
| | 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. PLANS AND |
| | DETAILS SUBMITTED ELECTRONICALLY SHALL BEAR DIGITAL |
| | SIGNATURES AND SEALS- SEE FBPE GUIDELINES BELOW. |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR |
| | ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND |
| | DOCUMENTS. |
| | A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL |
| | ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY |
| | CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION. |
| | THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE |
| | A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES |
| | NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.) |
| | |
| | A) PLEASE UPDATE THE CODE DATA LISTED ON THE TIE DOWN |
| | DETAIL TO INDICATE COMPLIANCE WITH THE THE FBC- 2020 |
| | CODES- SEC. 107.2.1 WPB. |
| | |
| | B) THE TIEDOWN DETAIL IS FOR AN UNDERGROUND TANK |
| | HOWEVER THE SUBMITTED SURVEY AND GOOGLE MAPS SHOW AN |
| | ABOVEGROUND TANK PROTECTED BY BOLLARDS. PLEASE CLARIFY |
| | WHAT TYPE OF TANK IS BEING INSTALLED- SEC. 107.2.1 WPB. |
| | |
| | C) PLEASE NOTE THAT THERE DOES NOT APPEAR TO BE |
| | EXISTING IMPACT PROTECTION ON THE WEST SIDE OF THE TANK |
| | WHICH IS ADJACENT TO A PARKING AREA- SEC. 303.4 FBC FG. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |