| Date |
Text |
| 2023-02-16 10:42:35 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE |
| | AT THE UTILITY CONNECTION AND THE GREASE TRAP REQUIRE |
| | SEPARATE PERMITS THAT ARE REQUIRED TO BE APPLIED FOR |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . AFTER YOU HAVE THE PERMIT(S) |
| | GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| | LETTER AND I WILL COMPLY THIS COMMENT. |
| | |
| | 2. 2020 FPC 607.1.1/613.1 - THE WATER HEATER AT THE |
| | JANITOR SINK SHALL HAVE A MIXING VALVE. ALL HOT WATER |
| | SHALL BE LIMITED BY SOMETHING OTHER THAN THE THERMOSTAT |
| | ON THE WATER HEATER. ADD A WATER HEATER DETAIL AS WELL |
| | AS ADD IT TO THE ISOMETRIC. |
| | |
| | 3. 2020 FPC 901.2.1 - PROVIDE A VENT FOR THE JANITOR |
| | SINK AND DRINKING FOUNTAIN. |
| | |
| | 4. 2020 FPC 906.1 - IT APPEARS T YOU NEED AT THE |
| | MINIMUM A 3" VENT STACK TO THE DOWNSTAIRS TENANT.THE |
| | VENT STACK SERVING A 6" BUILIDNG DRAIN CANNOT BE LESS |
| | THAN HALF ITS SIZE. |
| | |
| | 5. 2020 FPC 1003.4 - PLEASE SHOW THE OIL ALARM OR OIL |
| | SEPARATOR FOR THE SUMP IN THE ELEVATOR SHAFT. |
| | |
| | 6. 2020 FPC 712.3.2/906.5 - PLEASE DETAIL A VENT FOR |
| | THE SUMP PIT. |
| | |
| | 7. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE ADD A DETAIL |
| | AND SIZE FOR THE SCUPPERS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |