| 2023-02-23 13:18:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | FIRE HAS NO OBJECTIONS TO THE FRAMING DETAILS HOWEVER, |
| | ADDITIONAL INFO IS NEEDED FOR THE FINAL INSTALL. |
| | |
| | 1) THERE IS AN INDICATION OF THE CANOPY COVER MATERILA |
| | AND/OR A FLAME RATING CERTIFICATE. |
| | |
| | 25.2.2 FLAME PROPAGATION PERFORMANCE. |
| | 25.2.2.1 ALL TENT FABRIC SHALL MEET THE FLAME |
| | PROPAGATION |
| | PERFORMANCE CRITERIA CONTAINED IN TEST METHOD 2 OF NFPA |
| | 701, |
| | STANDARD METHODS OF FIRE TESTS FOR FLAME PROPAGATION OF |
| | TEXTILES |
| | AND FILMS. [101: 11.11.2.1] |
| | 25.2.2.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE |
| | THAT THE TENT |
| | FABRIC MATERIALS HAVE THE REQUIRED FLAME PROPAGATION |
| | PERFORMANCE: |
| | (1) THE AHJ SHALL REQUIRE A CERTIFICATE OR OTHER |
| | EVIDENCE OF |
| | ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO THE AHJ. |
| | (2) THE AHJ SHALL REQUIRE A REPORT OF TESTS MADE BY |
| | OTHER |
| | INSPECTION AUTHORITIES OR ORGANIZATIONS ACCEPTABLE TO |
| | THE |
| | AHJ. [101: 11.11.2.2] |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 2) THERE IS NO SITE PLAN INDICATING THE PROPOSED |
| | LOCATION OF THE CANOPY. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS |
| | |
| | PLEASE PROVIDE A DETAILED SITE PLAN. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |