| Date |
Text |
| 2023-04-19 14:20:05 | RESIDENTIAL(R3)SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020491 |
| | 324 SUMMA ST |
| | |
| | |
| | PREVIOUS COMMENT: |
| | 3- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: ELECTRONIC SUBMITTALS NEED ENGINEER'S VERIFIABLE |
| | DIGITAL SIGNATURE. |
| | |
| | RESPONSE: |
| | ENGINEER'S DRAWINGS SUBMITTED HAVE A COPY OF THE |
| | ENGINEER???S DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE |
| | NOT ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A |
| | LICENSED ENGINEER NEED TO HAVE THE ORIGINAL VERIFIABLE |
| | DIGITAL SIGNATURE OF THE ENGINEER AS REQUIRED BY SEC. |
| | 61G15-23.004 FAC AND CHAPTER 471 F.S. |
| | |
| | ALSO, ENGINEER'S DIGITAL SIGNATURE DOESN'T SEEM TO |
| | COMPLY WITH THE REQUIREMENTS OF SEC. 61G15-23.004. IT |
| | DOESN'T HAVE THE REQUIRED TEXT BOX LANGUAGE. IT ONLY |
| | SHOWS DIGITALLY SIGNED BY DEWEY A. LEBLANC AND THE |
| | DATE. IT DOESN'T IDENTIFY THE ENGINEER'S LICENSE |
| | NUMBER. |
| | |
| | SEE SEC. 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING |
| | AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | AND RESUBMIT WITH VERIFIABLE DIGITAL SIGNATURE. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |