| 2023-03-21 18:40:36 | RESIDENTIAL (R3)BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020491 |
| | 324 SUMMA ST |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE |
| | AND TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH |
| | THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING |
| | BUILDING. |
| | |
| | 2- FBC R 703.4, FBC B 1405.4, A FLASHING DETAIL OR |
| | SPECIFICATION IS REQUIRED. THIS COMMENT CAN BE RESOLVED |
| | BY DOING ONE OF THE FOLLOWING: |
| | |
| | REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED |
| | AND NOTE THE CODE REFERENCE - EXAMPLE "FLASHING IN |
| | ACCORDANCE WITH FBC R 703.4/B 1405.4 WILL BE |
| | INSTALLED". |
| | PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS |
| | MAY INCLUDE MORE THAN ONE OPTION |
| | PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN |
| | ONE OPTION |
| | |
| | 3- WIND LOAD CALCULATIONS NEED TO HAVE ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: ELECTRONIC SUBMITTALS NEED ENGINEER'S VERIFIABLE |
| | DIGITAL SIGNATURE. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |