| Plan Review Notes For Permit 23020478 |
| Permit Number |
23020478 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-19 11:43:32 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC 107.2.1 | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR DOORS, | | | WINDOW SYSTEMS AND ROOFING SYSTEMS LISTED ON THE | | | DRAWINGS. | | | | | | 2) PLEASE SHOW EXTERIOR WALL CLADDING ATTACHMENTS TO | | | THE STEEL FRAMING (ATTACHMENT TYPE, SIZE AND ON CENTER | | | SPACING) OR PROVIDE A PRODUCT APPROVAL FOR THE WALL | | | CLADDING SYSTEM - FBC WPB 107.2.1 | | | | | | 3) WINDOW, DOOR, ROOFING SYSTEM AND EXTERIOR WALL | | | CLADDING SYSTEMS MAY BE DEFERRED SUBMITTALS BY LISTING | | | ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - | | | FBC WPB 107.3.4.1 | | | | | | |
|