| 2023-02-14 12:09:38 | ELECTRIC PLAN REVIEW FAILED |
| | |
| | 1) PLEASE PROVIDE AN ELECTRIC FLOOR PLAN DETAILING ALL |
| | ELECTRIC WORK. CLEARLY DISTINGUISH NEW WORK VERSUS WORK |
| | THAT IS EXISTING AND TO REMAIN. PLEASE INCLUDE ALL |
| | SWITCHES, RECEPTACLES, APPLIANCES, AIR CONDITIONING, |
| | WATER HEATERS, ELECTRIC PANELS AND METERS. |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | 2) PLEASE PROVIDE AN ELECTRIC PANEL SCHEDULE DETAILING |
| | ALL CIRCUITS REQUIRED, CONDUCTOR SIZES AND OVERCURRENT |
| | PROTECTION FOR EACH CIRCUIT. PLEASE INDICATE WHETHER |
| | CIRCUIT IS NEW OR EXISTING. |
| | |
| | FBC 107.2 AND NEC 215.5 |
| | |
| | 3) PLEASE PROVIDE AN ACCURATE ELECTRIC RISER DETAILING |
| | ELECTRIC PANEL, CONDUIT, CONDUCTOR AND OVERCURRENT |
| | PROTECTION SIZES. PLEASE INDICATE EQUIPMENT AS NEW OR |
| | EXISTING. |
| | |
| | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| | THE FEEDERS. |
| | |
| | 4) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY |
| | WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC |
| | FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT |
| | RECEPTACLE REQUIREMENTS. |
| | |
| | 5) PROVIDE AN ELECTRIC LOAD CALCULATION DETAILING ALL |
| | ELECTRIC LOADS, AND APPLIANCES SUCH AS WATER HEATERS, |
| | RANGES, AIR CONDITIONING EQUIPMENT, ETC. |
| | |
| | NEC 220.40, THE CALCULATED LOAD OF A FEEDER OR SERVICE |
| | SHALL NOT BE LESS THAN THE SUM OF THE LOADS ON THE |
| | BRANCH CIRCUITS SUPPLIED |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |