| Plan Review Notes For Permit 23020394 |
| Permit Number |
23020394 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-17 09:05:25 | FIRE PROVISO COMMENTS: | | | | | | (1) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE | | | ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF | | | DEMOLITION AND CONSTRUCTION. | | | | | | (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | | FIRE WATCH. | | | | | | | | | (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL | | | DAMAGE DURING ALL PHASES OF DEMOLITION AND | | | CONSTRUCTION. | | | | | | (4) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND./OR FIRE ALARM) SHALL BE CONDUCTED BY | | | PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|