| 2023-06-16 18:43:10 | RESIDENTIAL(R3) RE-ROOF SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020356 |
| | 6132 UNITED ST |
| | |
| | 1-ROOF TILE NOA 22-0201.07 AND ROOF TILE ADHESIVE NOA |
| | 21-1006.03 SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE |
| | TO BE USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING |
| | PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| | OF SEC R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: SYSTEM ON PAGE 7 AS NOTED ON TILE BOND NOA |
| | DOESN'T MATCH TILE PROFILE. COORDINATE PADDY SIZE AND |
| | ROOF TILE PROFILE WITH ROOF TILE NOA TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | THE APPLICATION STATUS FOR NEW FLORIDA PRODUCT APPROVAL |
| | FL7849-R17 SUBMITTED SAYS "APPLIED FOR". IT IS NOT |
| | APPROVED YET. NEED APPROVED PRODUCT APPROVAL. |
| | FAC 61G20.3.001 |
| | |
| | |
| | 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED. |
| | GENERAL LIMITATIONS ON PAGE 5 OF 7 DON'T LIST TILE BOND |
| | ADHESIVE AS ONE OF THE ADHESIVES APPROVED TO BE USED |
| | WITH THIS UNDERLAYMENT. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR UNDERLAYMENT THAT ALLOWS TILE BOND TO BE |
| | USED. |
| | F.A.C. 61G20.3.001. |
| | |
| | RESPONSE: |
| | A)NEED TO MARK/SPECIFY ON NEW FLORIDA PRODUCT APPROVAL |
| | FL22525-R6 SUBMITTED WHICH APPROVED ASSEMBLY IS GOING |
| | TO BE INSTALLED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B)IT IS NOT CLEAR WHICH UNDERLAYMENT IS GOING TO BE |
| | INSTALLED. FLORIDA PRODUCT APPROVAL FL22525-R6 |
| | SUBMITTED IS HIGHLIGHTED WITH POLYSTICK MTS PLUS ON |
| | TABLE 2 BUT IT IS S HIGHLIGHTED WITH POLYSTICK TU MAX |
| | ON TABLE 2 ON PAGE 4 OF 9. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C)CLEARLY IDENTIFY WHICH SUBSTRATE OPTION FROM TABLE 3 |
| | ON PAGE 5 OF 9 OF FLORIDA PRODUCT APPROVAL FL22525-R6 |
| | SUBMITTED IS GOING TO BE INSTALLED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | TOWNHOUSE ROOF SHEATHING INFORMATIONAL NOTE: |
| | 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT REQUIRES A |
| | MINIMUM OF 5/8" THICK AND 4'-0" WIDE FIRE RETARDANT |
| | PLYWOOD SHEATHING BETWEEN UNITS. |
| | |