| 2023-05-26 18:25:46 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020356 |
| | 6132 UNITED ST |
| | |
| | 1-ROOF TILE NOA 22-0201.07 AND ROOF TILE ADHESIVE NOA |
| | 21-1006.03 SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE |
| | TO BE USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING |
| | PERMITS TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| | OF SEC R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: SYSTEM ON PAGE 7 AS NOTED ON TILE BOND NOA |
| | DOESN'T MATCH TILE PROFILE. COORDINATE PADDY SIZE AND |
| | ROOF TILE PROFILE WITH ROOF TILE NOA TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 2- POLYGLASS UNDERLAYMENT NOA 21-1217.02 SUBMITTED. |
| | GENERAL LIMITATIONS ON PAGE 5 OF 7 DON'T LIST TILE BOND |
| | ADHESIVE AS ONE OF THE ADHESIVES APPROVED TO BE USED |
| | WITH THIS UNDERLAYMENT. NEED TO PROVIDE PRODUCT |
| | APPROVAL FOR UNDERLAYMENT THAT ALLOWS TILE BOND TO BE |
| | USED. |
| | F.A.C. 61G20.3.001. |
| | |
| | 3- HIP AND RIDGE TILE INSTALLATION. PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS FOR HIP AND RIDGE |
| | INSTALLATION AS REQUIRED BY SEC. R905.3.7.1 |
| | FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS IN ACCORDANCE |
| | WITH FRSA/TRI FLORIDA HIGH WIND CONCRETE AND CLAY TILE |
| | INSTALLATION MANUAL (6TH EDITION) OR THE |
| | RECOMMENDATIONS OF RAS 118, 119 OR 120. |
| | ALTERNATIVE: IF USING METAL SUPPORT, THEN PROVIDE |
| | PRODUCT APPROVAL FOR HIP AND RIDGE METAL SUPPORT AND |
| | CLEARLY MARK ATTACHMENT METHOD. |
| | |
| | TOWNHOUSE ROOF SHEATHING INFORMATIONAL NOTE: |
| | 4- TOWNHOUSE ROOF SHEATHING REPLACEMENT REQUIRES A |
| | MINIMUM OF 5/8" THICK AND 4'-0" WIDE FIRE RETARDANT |
| | PLYWOOD SHEATHING BETWEEN UNITS. |
| | |
| | 5- CLARIFY WHY SUBMITTING NOA FOR SHINGLES. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |