Plan Review Notes
Plan Review Notes For Permit 23020340
Permit Number 23020340
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-03-30 10:58:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF THE OCCUPANCY
 CLASSIFICATION OF BOTH SPACES AND THE INTENT OF THE
 OCCUPANCY.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE OCCUPANCY DETAILS.
  
  
 2) THERE IS NO INDICATION OF NUMBER OF EXITS AND TRAVEL
 DISTANCES IN COMPLINACE WITH THE OCCUPANCY
 CLASSIFICATION NOTED IN # 1.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING COMPLIANCE
 WITH APPLICABLE CODE WITHIN NFPA 101.
  
  
  
 3) IT APPEARS THAT THE PROPOSED OPENING IS WITHIN A
 FIRE RATED SEPARATION, HOWEVER, THERE IS NO INDICATION
 OF THE NUMERICAL CALL OUT FOR THE # 1 TYP WALL TYPE
 THOUGH ITS A CMU.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 IF IT IS A REUIRED FIRE RATED SEPARATION THE OPENING IS
 REQUIRED TO HAVE THE SAME FIRE RATING.
  
 PLEASE PROVIDE THE WALL TYPE DETAILS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL