| 2023-03-20 19:02:29 | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020329 |
| | 345 SUMMA ST |
| | |
| | 1- PLANS SUBMITTED DON'T SHOW PROPOSED LOCATION OF |
| | CANTILEVERED STRUCTURE. PROVIDE PLANS WITH PROPOSED |
| | LOCATION. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ENGINEER'S LETTER APPROVING OFFSET COLUMNS ON SPREAD |
| | FOOTINGS: |
| | A) LETTER NEEDS TO IDENTIFY THE CANTILEVERED STRUCTURE. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | B) THE LETTER HAS A COPY OF THE ENGINEER'S |
| | SEAL/SIGNATURE. NEED TO HAVE THE ORIGINAL SIGNATURE OF |
| | THE ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 F.S. |
| | WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | DRAWINGS AND LETTERS WERE SUBMITTED ELECTRONICALLY. |
| | ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| | SIGNATURE. |
| | |
| | ENGINEERS |
| | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |