| Plan Review Notes For Permit 23020256 |
| Permit Number |
23020256 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-03-17 07:47:09 | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | SUBMITTED THIS CYCLE SPECS THE AHU-1 AS A 3 - TON | | | SYSTEM AND AHU - 2 AS A 3 - TON SYSTEM BUT THE | | | EQUIPMENT SCHEDULE ON THE M-1 SHEET SPECS. EACH UNIT TO | | | BE A 5 - TON UNIT. THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS AND THE EQUIPMENT SCHEDULE MUST BE WITHN | | | THE 1.15 TIMES SIZING ACCORDING TO: FEC R403.7.1.2 | | | | | | 2) THE KITCHEN HOOD MAY REQUIRE MAKE-UP AIR. FRC | | | M1503.4 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|