2023-02-24 15:02:01NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE - FBC
 R807.1 THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN
 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER LOCATION WITH READY
 ACCESS.
  
 2) DRAFT STOP IS SHOWN IN THE ROOF TRUSSES - WHICH WILL
 REQUIRE 2 ATTIC ACCESS. DRAFT STOP IS NOT REQUIRED IN
 THE ATTIC.
  
 3) PLEASE SHOW THE DRAFT STOP IN THE FLOOR TRUSSES PER
 - FBC R302.12 DRAFTSTOPPING.
 IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE
 BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A
 FLOOR-CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE
 THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS.
  
 4) PLEASE PROVIDE THE DOCUMENTATION (ICC EVALUATION
 REPORT) FOR THE ICYNENE FOAM INSULATION - FBC R316.3
  
 5) PRODUCT APPROVAL (NOA 20-0429.11) FOR THE SLIDING
 GLASS DOOR IS NOT ON THE LIST SHOWN ON THE WINDOW/DOOR
 SCHEDULE AND IS APPROVED FOR SMALL MISSILE IMPACT WHICH
 IS GLAZING ABOVE 30' ELEVATION - PLEASE PROVIDE THE
 SHUTTER PRODUCT APPROVAL FOR THIS SLIDING GLASS DOOR -
 FBC R301.2.1.2
  
 6) PRODUCT APPROVAL (FL16107-R13) FOR THE OVERHEAD
 GARAGE DOOR HAS A MAXIMUM WIDTH OF 9' - THE PROPOSED
 OVERHEAD GARAGE DOOR SHOWN ON THE DRAWING IS 16' -
 PLEASE PROVIDE A PRODUCT APPROVAL FOR THE 16' WIDE
 DOOR. PLEASE REVISE THE PRODUCT APPROVALS ON THE
 WINDOW/DOOR SCHEDULE.
  
 7) PRODUCT APPROVAL (FL21138.12) FOR THE SWING DOOR HAS
 A MAXIMUM DESIGN PRESSURE OF (-50) PLEASE SHOW THE
 LOCATION FOR THESE DOORS - SOME OF THE EXTERIOR DOORS
 SHOWN ON THE WINDOW/DOOR SCHEDULE DRAWING SHOW THAT A
 HIGHER PRESSURE IS REQUIRED.
  
 8) PLEASE DESCRIBE HOW THE ROOF COMPONENTS (TILE -
 UNDERLAYMENT) ARE ATTACHED OR CIRCLE THE ROOF SYSTEM
 ATTACHMENTS IN THE PRODUCT APPROVALS - IF USING
 ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
 FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER CERTIFYING SUITABILITY FOR
 THE SPECIFIC SITE MUST BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS