| 2023-02-23 15:49:28 | SFR REMODEL |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE AN EXTERIOR WINDOW AND DOOR FLASHING |
| | DETAIL - FBC R703.1.1 WATER RESISTANCE. |
| | THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND |
| | CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION |
| | OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A |
| | WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS |
| | REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO |
| | THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR |
| | CLADDING. |
| | EXCEPTIONS: 1. A WEATHER-RESISTANT EXTERIOR WALL |
| | ENVELOPE SHALL NOT BE REQUIRED OVER CONCRETE OR MASONRY |
| | WALLS DESIGNED IN ACCORDANCE WITH CHAPTER 6 AND FLASHED |
| | IN ACCORDANCE WITH SECTION R703.4. |
| | |
| | 2) PLEASE SHOW THE REQUIRED SMOKE DETECTOR LOCATIONS - |
| | FBC R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 3) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY |
| | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |