Plan Review Notes
Plan Review Notes For Permit 23020134
Permit Number 23020134
Review Stop B
Sequence Number 3
Notes
Date Text
2023-06-16 13:30:41NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE CLOSET STANDS ALONE AS AN ENCLOSURE - THE GARAGE
 WILL NEED ADDITIONAL FLOOD VENTS TO EQUAL THE REQUIRED
 SQUARE INCHES OF FLOOD VENTS - FBC R322.2.2
  
 2) PLEASE PROVIDE THE SMART FLOOD VENT ICC EVALUATION
 REPORT AND THE PRODUCT APPROVAL. FBC WPB 107.1
  
 3) ELEVATION CERTIFICATE - NEEDS CORRECTIONS - PER FEMA
 ELEVATION CERTIFICATE INSTRUCTIONS
  
 A8(A) - THE CLOSET IS AN ENCLOSURE - SHOW THE CLOSET
 SQUARE FOOTAGE
 A8(B) - SHOW THE NUMBER OF FLOOD VENTS FOR THIS
 ENCLOSURE
 A8(C) - SHOW THE AREA OF FLOOD VENTS FOR THE ENCLOSURE
 A9(B) - SHOW HOW MANY FLOOD VENTS FOR THE GARAGE
 A9(C) - SHOW THE TOTAL OPEN AREA OF THE FLOOD VENTS FOR
 THE GARAGE
 A9(D) - SMART VENT IS AN ENGINEERED VENT
 C2(A) - WOULD BE THE ENCLOSURE ELEVATION
 C2(B) - WOULD BE THE NEXT HIGHER FLOOR
 C2(E) - SHOW THE EQUIPMENT ELEVATION.
 THE ELEVATION CERTIFICATE WILL NEED TO BE DIGITALLY
 SIGNED BY THE SURVEYOR - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  
  
  
  
  