2023-03-31 13:19:16NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE SIZE AND LOCATIONS OF THE REQUIRED
 FLOOD VENTS FOR THE GARAGE AND AC CLOSET - FBC R322.2.2
  
 2) PLEASE SHOW THE EQUIPMENT (AC) ELEVATIONS - FBC
 R322.1.6
  
 3) PLEASE PROVIDE DETAILS FOR THE ROOF TILE ATTACHMENT
 - FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED
  
 4) ELEVATION CERTIFICATE - NEEDS CORRECTIONS -
 A5 - THE LONGITUDE NUMBER SHOULD BE A NEGATIVE NUMBER.
 A9(B) - SHOW HOW MANY FLOOD VENTS.
 A9(C) - SHOW THE TOTAL OPEN AREA OF THE FLOOD VENTS.
 B1 - INCLUDE THE COMMUNITY NUMBER.
 C2(D) - THE ELEVATION NUMBER APPEARS TO BE INCORRECT -
 THERE IS A DROP OF 4" ON DRAWING A-1 AND A DROP OF 5
 1/2" ON DRAWING S-1
 C2(E) - SHOW THE EQUIPMENT ELEVATION.
 SECTION "D" DESCRIBE THE TYPE OF EQUIPMENT
  
 5) THE PAVING, GRADING AND DRAINAGE PLAN DOES NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  