| Plan Review Notes For Permit 23020134 |
| Permit Number |
23020134 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-03 13:50:57 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. UPSTAIRS BATHROOMS - NOT MORE THAN ONE WET-VENTED | | | FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE | | | DRY-VENTED FIXTURE DRAIN CONNECTION. FOR ALL 3 | | | BATHROOMS UPSTAIRS, THE WATER CLOSET AND SHOWER OR TUB | | | ARE CONNECTING ON THE HIGH SIDE OF THE VENTED FIXTURES | | | CONNECTION. ONLY ONE IS ALLOWED. | | | | | | 2. DOWNSTAIRS BATHROOM - 2020 FPC P3104.4 - THE DRY | | | VENT FOR THE TWO SHOWER TRAPS IS NOT ALLOWED TO BE | | | HORIZONTAL UNTIL IT IS 6" ABOVE THE FLOOD RIM OF THE | | | FIXTURES SERVED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|