Plan Review Notes
Plan Review Notes For Permit 23020134
Permit Number 23020134
Review Stop M
Sequence Number 1
Notes
Date Text
2023-02-06 06:17:171ST REVIEW FMC
 PERMIT: 23020134
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE EXPLAIN WHY THE AHU IS NOT LISTED ON THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS.
  
 2) PROVIDE SIZES FOR ALL FLEX DUCT ON THE DRAWINGS. FBC
 107.3.5
  
 3) SHEETS M-1 AND M-2: THE DRYER EXHAUST MATERIAL SHALL
 BE 28 GAUGE METAL. FRC M1502.4.1
  
 4) PLEASE PROVIDE A RETURN AIR PATH BACK TO AHU-1 FROM
 THE MASTER BEDROOM WHEN THE MASTER BEDROOM DOORS ARE
 CLOSED. FRC M1602.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  