| Plan Review Notes For Permit 23020134 |
| Permit Number |
23020134 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-06 06:17:17 | 1ST REVIEW FMC | | | PERMIT: 23020134 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE EXPLAIN WHY THE AHU IS NOT LISTED ON THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. | | | | | | 2) PROVIDE SIZES FOR ALL FLEX DUCT ON THE DRAWINGS. FBC | | | 107.3.5 | | | | | | 3) SHEETS M-1 AND M-2: THE DRYER EXHAUST MATERIAL SHALL | | | BE 28 GAUGE METAL. FRC M1502.4.1 | | | | | | 4) PLEASE PROVIDE A RETURN AIR PATH BACK TO AHU-1 FROM | | | THE MASTER BEDROOM WHEN THE MASTER BEDROOM DOORS ARE | | | CLOSED. FRC M1602.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|