| Plan Review Notes For Permit 23020129 |
| Permit Number |
23020129 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-30 08:24:11 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PANEL "B IS IN THE SEPARATE STRUCTURE AND 225.33 | | | REQUIRES A MAIN BREAKER WHEN MORE THAN 6 BREAKERS ARE | | | MOUNTED IN THAT PANEL. | | | | | | 225.33 MAXIMUM NUMBER OF DISCONNECTS. | | | (A) GENERAL. | | | | | | THE DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY | | | 225.30 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR | | | SIX CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN | | | A GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A | | | SWITCHBOARD OR SWITCHGEAR. THERE SHALL BE NO MORE THAN | | | SIX DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION. |
|