Plan Review Notes
Plan Review Notes For Permit 23020129
Permit Number 23020129
Review Stop E
Sequence Number 2
Notes
Date Text
2023-06-30 08:24:11FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PANEL "B IS IN THE SEPARATE STRUCTURE AND 225.33
 REQUIRES A MAIN BREAKER WHEN MORE THAN 6 BREAKERS ARE
 MOUNTED IN THAT PANEL.
  
 225.33 MAXIMUM NUMBER OF DISCONNECTS.
 (A) GENERAL.
  
 THE DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY
 225.30 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR
 SIX CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN
 A GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A
 SWITCHBOARD OR SWITCHGEAR. THERE SHALL BE NO MORE THAN
 SIX DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION.