| 2023-06-26 13:54:34 | BUILDING REVIEW COMMENTS FOR GARAGE PORTION: FAILED | | | | | | W.P.B. PERMIT:23020128 | | | | | | REVIEWED: 6.26.2023 | | | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC BUILDING | | | FBC EXISTING BUILDING | | | | | | COMMENTS: | | | | | | | | | SEE GARAGE PERMIT 23020129 FOR ADDITIONAL FEES | | | | | | SHEET A-1 | | | | | | 1. AS PER FBC 107.2.1 CLARIFY | | | DOOR TAGS ARE NOT COORDINATED WITH DOOR SCHEDULE. | | | PROVIDE NOA AND DESIGN PRESSURE FOR ALL NEW EXTERIOR | | | DOORS INCLUDING GARAGE DOORS IN THE SCHEDULE JUST LIKE | | | PRESENTED FOR THE WINDOWS. PLEASE UDATE AND RESUBMIT. | | | | | | END OF BUILIDNG COMMENTS | | | | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | | HESITATE TO CONTACT ME | | | | | | LOUIS BOND, AIA | | | BUILDING PLANS EXAMINER II | | | DEVELOPMENT SERVICES DEPT. | | | BUILDING DIVISION | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FLORIDA 33401 | | | PH: 561-805-6729 | | | FX: 561-805-6676 | | | EMAIL: [email protected] | | | | | | | | | NOTES: | | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | | EACH COMMENT IS BEING ADDRESSED. | | | |
|