| 2023-05-15 10:07:29 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) GARAGE PANEL NEEDS A GROUNDING ELECTRODE SYSTEM | | | 250.32 | | | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | | OR BRANCH CIRCUIT(S). | | | (A) GROUNDING ELECTRODE. | | | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR | | | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | | PART III OF ARTICLE 250. THE GROUNDING ELECTRODE | | | CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH | | | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING | | | ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN | | | 250.50 SHALL BE INSTALLED. | | | | | | 2) GARAGE PANEL WILL NEED A MAIN BREAKER 225.33 | | | | | | 225.33 MAXIMUM NUMBER OF DISCONNECTS. | | | (A) GENERAL. | | | THE DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY | | | 225.30 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR | | | SIX CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN | | | A GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A | | | SWITCHBOARD OR SWITCHGEAR. THERE SHALL BE NO MORE THAN | | | SIX DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION. |
|