Plan Review Notes
Plan Review Notes For Permit 23020128
Permit Number 23020128
Review Stop E
Sequence Number 1
Notes
Date Text
2023-05-15 10:07:29FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) GARAGE PANEL NEEDS A GROUNDING ELECTRODE SYSTEM
 250.32
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED.
  
 2) GARAGE PANEL WILL NEED A MAIN BREAKER 225.33
  
 225.33 MAXIMUM NUMBER OF DISCONNECTS.
 (A) GENERAL.
 THE DISCONNECTING MEANS FOR EACH SUPPLY PERMITTED BY
 225.30 SHALL CONSIST OF NOT MORE THAN SIX SWITCHES OR
 SIX CIRCUIT BREAKERS MOUNTED IN A SINGLE ENCLOSURE, IN
 A GROUP OF SEPARATE ENCLOSURES, OR IN OR ON A
 SWITCHBOARD OR SWITCHGEAR. THERE SHALL BE NO MORE THAN
 SIX DISCONNECTS PER SUPPLY GROUPED IN ANY ONE LOCATION.