| 2023-04-12 16:05:30 | 1ST REVIEW FMC | | | PERMIT: 23020122 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE ON THE MECHANICAL DEMO DRAWINGS, THE SIZES | | | OF THE BOILERS BEING REPLACED ALONG WITH THE FUEL | | | SOURCE FOR THESE EXISTING BOILERS. PROVIDE THE NEW | | | BOILER SIZES AND FUEL TYPE ON THE NEW DESIGN DRAWINGS. | | | FBC 107.3.5 | | | | | | 2) SHEET M801 INDICATES THAT THE FUEL SOURCE FOR B-1 | | | AND B-2 TO BE FUEL OIL. SHEET M704 HAS A NATURAL GAS | | | DETECTOR DETAIL DRAWING. WHAT IS THIS FOR? IF IT | | | ISN???T NEEDED PLEASE REMOVE. FBC 107.3.5 | | | | | | 3) PROVIDE THE COMBUSTION AIR CALCULATIONS FOR THESE | | | BOILERS. FMC 701.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|