| 2023-04-10 10:27:54 | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | ELECTRICAL REVIEW STATUS: PASS, SEE COMMENTS BELOW |
| | |
| | 1. AVAILABLE FAULT CURRENT |
| | NEC 110.24 STATES: FIELD MARKING. SERVICE EQUIPMENT IN |
| | OTHER THAN DWELLING UNITS SHALL BE LEGIBLY MARKED IN |
| | THE FIELD WITH THE MAXIMUM AVAILABLE FAULT CURRENT. THE |
| | FIELD MARKING(S) SHALL INCLUDE THE DATE THE FAULT |
| | CURRENT CALCULATION WAS PERFORMED AND BE OF SUFFICIENT |
| | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. |
| | |
| | 2. WORKING SPACE |
| | NEC TABLE 110.26(A) OR IRC E3405.2 |
| | SECTION 110.26 REQUIRES ADEQUATE WORKING SPACE FOR ALL |
| | ELECTRICAL EQUIPMENT. NEC SECTION 110.26(A) REQUIRES A |
| | CLEAR SPACE AT LEAST 30 INCHES WIDE AND 36 INCHES DEEP |
| | IF THE EQUIPMENT IS LIKELY TO BE WORKED ON WHILE |
| | ENERGIZED. |
| | |
| | 3. ELECTRICAL PANEL |
| | NEC 110.3(B) INSTALLATION AND USE. EQUIPMENT THAT IS |
| | LISTED, LABELED, OR BOTH SHALL BE INSTALLED AND USED IN |
| | ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE |
| | LISTING OR LABELING. |
| | |
| | 4. NEC SECTION 110.26 SPACES ABOUT ELECTRICAL EQUIPMENT |
| | (A) ELECTRICAL PANELS MUST BE ACCESSIBLE |
| | (B) ELECTRICAL PANELS MUST BE REACHABLE |
| | (C) OCCUPANTS MUST HAVE READY ACCESS |
| | (D) ELECTRICAL PANELS CANNOT BE EXPOSED TO PHYSICAL |
| | DAMAGE |
| | (E) ELECTRICAL PANELS SHOULD BE CLEAR OF FLAMMABLE |
| | MATERIAL |
| | |
| | 5. NEC 110.14(D) CONDUCTOR TERMINATION, TORQUE - WHERE |
| | TIGHTENING TORQUE VALUES ARE INDICATED ON EQUIPMENT OR |
| | INSTALLATION INSTRUCTIONS, A CALIBRATED TORQUE TOOL |
| | MUST BE USED TO ACHIEVE THE INDICATED TORQUE VALUE, |
| | UNLESS THE EQUIPMENT MANUFACTURER PROVIDES AN |
| | ALTERNATIVE METHOD OF ACHIEVING THE REQUIRED TORQUE. |
| | |
| | END OF COMMENTS |
| | |