Plan Review Notes
Plan Review Notes For Permit 23020116
Permit Number 23020116
Review Stop E
Sequence Number 3
Notes
Date Text
2023-04-24 12:24:19ELECTRIC REVIEW FAILED
  
 1) ELECTRICAL RESPONSE FROM ENGINEER OF RECORD STATES
 SHEET INCORRECTLY STATES THAT ALL NEW ELECTRIC IS
 INSTALLED. THIS PLAN REVIEWER FINDS NOTES STATING ONLY
 NEW ELECTRIC WORK IS IN STORAGE ROOM AND BEDROOM 1.
 PLEASE CORRECT AS APPLICABLE. FBC 107.2
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 2) ENGINEER OF RECORD STATES FURTHER AS FOLLOWS. PLEASE
 INDICATE ALL NEW ELECTRIC IS INSTALLED ON SHEET EP-1.
 PLEASE PROVIDE CLARITY AS TO WHAT THIS STATEMENT MEANS
 PLEASE CORRECT AS APPLICABLE. FBC 107.2
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 3) PLEASE PROVIDE AN ELECTRIC RISER DETAILING METER,
 DISCONNECTS, ELECTRIC PANELS, CONDUIT, CONDUCTOR AND
 OVERCURRENT PROTECTION SIZES. PLEASE INDICATE EQUIPMENT
 AS NEW OR EXISTING. NEC 215.5
  
 4) SHEET EP-1 STATES THER IS AN EXISTING REMOTE LAUNDRY
 STRUCTURE. A REVIEW OF PREVIOUS PERMITS AND PROPERTY
 APPRAISER RECORDS DO NOT DETAIL A REMOTE STRUCTURE ON
 THE PROPERTY. PLEASE PROVIDE DOCUMENTS DETAILING THE
 STRUCTURE WAS PERMITED . FBC 107.2
  
 5) IF THE REMOTE STRUCTURE WAS PERMITTED PLEASE DETAIL
 COMPLIANCE WITH NEC 225.30
  
 NEC 225.30 A BUILDING OR OTHER STRUCTURE THAT IS SERVED
 BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE FEEDER OR BRANCH CIRCUIT
  
 6) IF THERE IS AN ADDITIONAL ELECTRIC PANEL AT THE
 REMOTE STRUCTURE PLEASE DETAIL THIS PANEL IN THE RISER
 DIAGRAM ALONG WITH THE REQUIRED GROUNDING ELECTRODE
 SYSTEM AS REQUIRED PER NEC 250.32
  
 NEC 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A
 FEEDER(S) OR BRANCH CIRCUIT(S).
 (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  