| 2023-04-24 12:24:19 | ELECTRIC REVIEW FAILED |
| | |
| | 1) ELECTRICAL RESPONSE FROM ENGINEER OF RECORD STATES |
| | SHEET INCORRECTLY STATES THAT ALL NEW ELECTRIC IS |
| | INSTALLED. THIS PLAN REVIEWER FINDS NOTES STATING ONLY |
| | NEW ELECTRIC WORK IS IN STORAGE ROOM AND BEDROOM 1. |
| | PLEASE CORRECT AS APPLICABLE. FBC 107.2 |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | 2) ENGINEER OF RECORD STATES FURTHER AS FOLLOWS. PLEASE |
| | INDICATE ALL NEW ELECTRIC IS INSTALLED ON SHEET EP-1. |
| | PLEASE PROVIDE CLARITY AS TO WHAT THIS STATEMENT MEANS |
| | PLEASE CORRECT AS APPLICABLE. FBC 107.2 |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | 3) PLEASE PROVIDE AN ELECTRIC RISER DETAILING METER, |
| | DISCONNECTS, ELECTRIC PANELS, CONDUIT, CONDUCTOR AND |
| | OVERCURRENT PROTECTION SIZES. PLEASE INDICATE EQUIPMENT |
| | AS NEW OR EXISTING. NEC 215.5 |
| | |
| | 4) SHEET EP-1 STATES THER IS AN EXISTING REMOTE LAUNDRY |
| | STRUCTURE. A REVIEW OF PREVIOUS PERMITS AND PROPERTY |
| | APPRAISER RECORDS DO NOT DETAIL A REMOTE STRUCTURE ON |
| | THE PROPERTY. PLEASE PROVIDE DOCUMENTS DETAILING THE |
| | STRUCTURE WAS PERMITED . FBC 107.2 |
| | |
| | 5) IF THE REMOTE STRUCTURE WAS PERMITTED PLEASE DETAIL |
| | COMPLIANCE WITH NEC 225.30 |
| | |
| | NEC 225.30 A BUILDING OR OTHER STRUCTURE THAT IS SERVED |
| | BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A |
| | SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY |
| | ONE FEEDER OR BRANCH CIRCUIT |
| | |
| | 6) IF THERE IS AN ADDITIONAL ELECTRIC PANEL AT THE |
| | REMOTE STRUCTURE PLEASE DETAIL THIS PANEL IN THE RISER |
| | DIAGRAM ALONG WITH THE REQUIRED GROUNDING ELECTRODE |
| | SYSTEM AS REQUIRED PER NEC 250.32 |
| | |
| | NEC 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A |
| | FEEDER(S) OR BRANCH CIRCUIT(S). |
| | (A) GROUNDING ELECTRODE. |
| | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR |
| | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| | GROUNDING ELECTRODE SYSTEM INSTALLED |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |