| Date |
Text |
| 2023-03-31 09:51:07 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 PLEASE CLARIFY; SUBMITTED APPROVED |
| | DRAWINGS INDICATES REROOFING LOWER BARREL TILE ROOF |
| | ONLY. IF ADDITIONAL REROOFING/ROOFING WILL BE PERFORMED |
| | INDICATE ON ROOF DRAWING AND CLEARLY IDENTIFY AREAS TO |
| | RECEIVE NEW ROOFING WITH ROOFING SYSTEM TO BE USED. |
| | SECOND REQUEST |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11288-R21 |
| | COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECTED |
| | ATTACHMENT LIMITATION SYSTEM #14 PAGE #7 DO NOT MEET OR |
| | EXCEED -85 MAXIMUM DESIGN PRESSURE REQUIREMENT. SELECT |
| | SYSTEM THAT MEETS OR EXCEEDS THIS REQUIREMENT. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SECOND |
| | REQUEST. |
| | 3. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| | APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| | PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| | SUBMITTING. REVIEW STAMP WITH INITIALS. SECOND REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |