| Plan Review Notes For Permit 23020090 |
| Permit Number |
23020090 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-21 13:41:58 | 1ST REVIEW FMC | | | PERMIT: 23020090 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THERE WERE 2 MECHANICAL PLANS SUBMITTED, 1 FROM | | | ALEXANDER ROJAS WHICH SHOWED ONLY THE MECHANICAL DESIGN | | | FOR THE NEW ADDITION. THE OTHER DRAWING WAS FROM AN | | | UNKNOW AUTHOR AS IT WASN???T SIGNED BY THE DESIGNER. | | | THIS DESIGN IS FOR THE ENTIRE HOUSE WHICH IS WHAT THE | | | ENERGY CALCS AND MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS WAS FOR. HOW EVER THIS DRAWING IS NOT | | | COMPLETE AS IT DOES NOT SHOW DOOR OR CASED OPENING. IT | | | ALSO DOES NOT SHOW THE RETURN AIR PATH FROM ROOMS WITH | | | DOORS BACK TO THE AHU. PROVIDE ONLY 1 COMPLETE DRAWING | | | FOR THIS PROJECT. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|