2023-02-21 13:41:581ST REVIEW FMC
 PERMIT: 23020090
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE WERE 2 MECHANICAL PLANS SUBMITTED, 1 FROM
 ALEXANDER ROJAS WHICH SHOWED ONLY THE MECHANICAL DESIGN
 FOR THE NEW ADDITION. THE OTHER DRAWING WAS FROM AN
 UNKNOW AUTHOR AS IT WASN???T SIGNED BY THE DESIGNER.
 THIS DESIGN IS FOR THE ENTIRE HOUSE WHICH IS WHAT THE
 ENERGY CALCS AND MECHANICAL EQUIPMENT SIZING
 CALCULATIONS WAS FOR. HOW EVER THIS DRAWING IS NOT
 COMPLETE AS IT DOES NOT SHOW DOOR OR CASED OPENING. IT
 ALSO DOES NOT SHOW THE RETURN AIR PATH FROM ROOMS WITH
 DOORS BACK TO THE AHU. PROVIDE ONLY 1 COMPLETE DRAWING
 FOR THIS PROJECT. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  