| 2023-02-03 12:00:29 | 1ST REVIEW FMC |
| | PERMIT: 23020072 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ON THE REVISION REQUEST FORM UNDER DESCRIPTION OF |
| | INFORMATION BEING SUBMITTED IT STATES ONLY SEE |
| | MECHANICAL DRAWINGS. ON THE MECHANICAL DRAWING |
| | SUBMITTED. IT APPEARS THE DIFFERENCE BETWEEN THE |
| | ORIGINALLY APPROVED DRAWING AND THIS LATEST DRAWING IS |
| | THE DUCT IS NOW WHAT APPEARS TO BE ALL FLEX DUCT. THERE |
| | IS ALSO A NEW AIR CONDITIONING SYSTEM SCHEDULE THAT |
| | INCLUDES AHU-1, AHU-2 AND AHU-3. ARE THESE TO BE NEW |
| | INSTEAD OF EXISTING NOW? IF SO, THE DRAWING STILL HAS |
| | THEM AS EXISTING, PLEASE CHANGE THIS. ALSO, ON THE |
| | REVISION FORM THE INCREASED VALUE OF WORK IS NOT FILLED |
| | IN. PROVIDE THE CORRECTED AMOUNT OF DOLLAR VALUE FOR |
| | ALL CHANGES. PROVIDE A SCOPE OF WORK FOR ALL CHANGES TO |
| | HELP THIS REVIEWER UNDERSTAND WHAT IS BEING CHANGED |
| | UNDER THIS REVISION. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |