| 2023-03-09 17:36:34 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23020061 |
| | 701 S OLIVE AVE |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- PLANS SUBMITTED NEED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT SHOWN ON PLANS AS REQUIRED BY 61G1-16.001FAC |
| | AND CHAPTER 481 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS |
| | FOR PUBLIC RECORDS. |
| | NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ARCHITECT'S |
| | VERIFIABLE DIGITAL SIGNATURE. |
| | |
| | ARCHITECTS |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2- DRAWING A2.02 SHOWS PORCELAIN TILE IN THE STAIRWAY |
| | NEXT TO ELEVATOR VESTIBULE #1. ARCHITECT TO PROVIDE |
| | COMPLETE STAIR DETAILS SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH STAIRS RISER/TREADS SEC. 1011.5 |
| | FBC-BUILDING. |
| | |
| | 3- SOUND TRANSMISSION. HARD FLOORING (CERAMIC TILE) |
| | NEEDS TO COMPLY WITH THE SOUND TRANSMISSION |
| | REQUIREMENTS OF SEC. 1207.1 FBC-BUILDING. NEED TO |
| | PROVIDE THE FOLLOWING FOR THE CERAMIC TILE SOUND |
| | INSULATION UNDERLAYMENT: |
| | |
| | (A)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | (B)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| | ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| | |
| | 4- CERAMIC TILE SOUND TRANSMISSION UNDERLAYMENT: |
| | PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| | (2020). |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| | SUBMITTAL DOCUMENTS PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |