| 2023-05-19 09:37:32 | NEW COMMERCIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PROVIDE THE CIVIL PLANS IF THEY WILL PROVIDE THE |
| | INFO NEEDED - PLEASE SHOW THE FOLLOWING ITEMS ON THE |
| | SITE PLAN PER - FBC WPB 107.2.5 SITE PLAN. THE |
| | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION |
| | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING |
| | TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND |
| | EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT |
| | LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED |
| | FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE |
| | AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND |
| | DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN |
| | ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY |
| | LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY |
| | PROPOSED WATER RETAINING SWALES) |
| | |
| | 2) ACCESSIBLE PARKING SPACE LOCATION PLEASE SHOW THE |
| | ACCESSIBLE PATH FROM THE ACCESSIBLE PARKING SPACE TO |
| | THE ACCESSIBLE ENTRY - FBC A208.3.1 PARKING SPACES |
| | COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR |
| | FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE |
| | ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4. |
| | |
| | 3) CANNOT HAVE A RAMP IN THE 5 FOOT PARKING ACCESS |
| | AISLE - FBC A 502.4 FLOOR OR GROUND SURFACES. |
| | PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL |
| | COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME |
| | LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN |
| | LEVEL ARE NOT PERMITTED. |
| | |
| | 4) DRAWING A.104 SHOWS THE RESTROOM WALL COVERING AS |
| | "WPT" (TILE) - DRAWING A.600 SHOWS THE RESTROOM WALL |
| | COVERING AS "WVP" (WOOD) - PLEASE CLEARIFY THE DRAWINGS |
| | SHOULD MATCH - IF USING "WOOD" PLEASE PROVIDE DOCUMENTS |
| | THAT SHOW THE WOOD VENEER COMPLIES WITH FBC 1210.2.2 |
| | WALLS AND PARTITIONS. WALLS AND PARTITIONS WITHIN 2 |
| | FEET (610 MM) OF SERVICE SINKS, URINALS AND WATER |
| | CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM) |
| | ABOVE THE FLOOR, |
| | |
| | 5) DRAWINGS SHOW THE BUILDING CONSTRUCTION TYPE AS IIB |
| | - PLEASE PROVIDE A NOTE ON THE DRAWINGS THAT THE |
| | EXTERIOR WOOD SHEATHING USED ON THE EXTERIOR WALL NEEDS |
| | TO BE FIRE RETARDANT PER FBC 603.1 |
| | |
| | 6) DRAWINGS LS.101, LS.102, A.101, A.102, A.600, A.602 |
| | DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - |
| | |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |
| | |
| | |
| | |
| | |
| | |