Plan Review Notes
Plan Review Notes For Permit 23020041
Permit Number 23020041
Review Stop B
Sequence Number 2
Notes
Date Text
2023-05-19 09:37:32NEW COMMERCIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PROVIDE THE CIVIL PLANS IF THEY WILL PROVIDE THE
 INFO NEEDED - PLEASE SHOW THE FOLLOWING ITEMS ON THE
 SITE PLAN PER - FBC WPB 107.2.5 SITE PLAN. THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING
 TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND
 EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT
 LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED
 FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE
 AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN
 ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY
 LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY
 PROPOSED WATER RETAINING SWALES)
  
 2) ACCESSIBLE PARKING SPACE LOCATION PLEASE SHOW THE
 ACCESSIBLE PATH FROM THE ACCESSIBLE PARKING SPACE TO
 THE ACCESSIBLE ENTRY - FBC A208.3.1 PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4.
  
 3) CANNOT HAVE A RAMP IN THE 5 FOOT PARKING ACCESS
 AISLE - FBC A 502.4 FLOOR OR GROUND SURFACES.
 PARKING SPACES AND ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE. CHANGES IN
 LEVEL ARE NOT PERMITTED.
  
 4) DRAWING A.104 SHOWS THE RESTROOM WALL COVERING AS
 "WPT" (TILE) - DRAWING A.600 SHOWS THE RESTROOM WALL
 COVERING AS "WVP" (WOOD) - PLEASE CLEARIFY THE DRAWINGS
 SHOULD MATCH - IF USING "WOOD" PLEASE PROVIDE DOCUMENTS
 THAT SHOW THE WOOD VENEER COMPLIES WITH FBC 1210.2.2
 WALLS AND PARTITIONS. WALLS AND PARTITIONS WITHIN 2
 FEET (610 MM) OF SERVICE SINKS, URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR,
  
 5) DRAWINGS SHOW THE BUILDING CONSTRUCTION TYPE AS IIB
 - PLEASE PROVIDE A NOTE ON THE DRAWINGS THAT THE
 EXTERIOR WOOD SHEATHING USED ON THE EXTERIOR WALL NEEDS
 TO BE FIRE RETARDANT PER FBC 603.1
  
 6) DRAWINGS LS.101, LS.102, A.101, A.102, A.600, A.602
 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  
  
  