Plan Review Notes
Plan Review Notes For Permit 23020041
Permit Number 23020041
Review Stop E
Sequence Number 1
Notes
Date Text
2023-02-15 08:35:28ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM. NEC 215.5
  
 2) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION. NEC
 215.5
  
 3) PLEASE PROVIDE AN ELECTRIC LIGHTING PLAN. FBC 107.2
  
 4) PLEASE PROVIDE A NOTE STAING , LOW VOLTAGE, FIRE
 ALRM, ACCESS CONTOL, SECURITY, AUDIO, VIDEO, SITE
 LIGHTING, SIGN, AND OTHER LOW VOLTAGE SYSTEM WIRING
 REQUIRE A SEPARATE PERMIT.
  
 5) PROVIDE A ROOF POWER PLAN AS APPLICABLE. FBC 107.2
  
 6) PROVIDE ACTUAL GROUNDING ELECTRODE AND OTHER
 GROUNDING CONDUCTOR SIZES FOR ELECTRICAL SERVICE. NOT
 JUST NEC CODE REFERENCES. NEC 250 FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  