| Plan Review Notes For Permit 23020041 |
| Permit Number |
23020041 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-15 08:35:28 | ELECTRIC REVIEW FAILED | | | | | | 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM. NEC 215.5 | | | | | | 2) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION. NEC | | | 215.5 | | | | | | 3) PLEASE PROVIDE AN ELECTRIC LIGHTING PLAN. FBC 107.2 | | | | | | 4) PLEASE PROVIDE A NOTE STAING , LOW VOLTAGE, FIRE | | | ALRM, ACCESS CONTOL, SECURITY, AUDIO, VIDEO, SITE | | | LIGHTING, SIGN, AND OTHER LOW VOLTAGE SYSTEM WIRING | | | REQUIRE A SEPARATE PERMIT. | | | | | | 5) PROVIDE A ROOF POWER PLAN AS APPLICABLE. FBC 107.2 | | | | | | 6) PROVIDE ACTUAL GROUNDING ELECTRODE AND OTHER | | | GROUNDING CONDUCTOR SIZES FOR ELECTRICAL SERVICE. NOT | | | JUST NEC CODE REFERENCES. NEC 250 FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|