| Date |
Text |
| 2023-05-12 11:29:12 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. NOT ADDRESSED. A BACKFLOW PERMIT AND AN INTERCEPTOR |
| | PERMIT MUST BE APPLIED FOR BEFORE THIS COMMENT CAN BE |
| | RELEASED. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW |
| | DEVICE AT THE UTILITY CONNECTION AND THE GREASE TRAP |
| | REQUIRE SEPARATE PERMITS THAT ARE REQUIRED TO BE |
| | APPLIED FOR PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected]. AFTER YOU HAVE THE PERMIT(S) |
| | GENERATED, NOTIFY ME VIA EMAIL OR NOTE IN THE RESPONSE |
| | LETTER AND I WILL COMPLY THIS COMMENT. |
| | A) DONE |
| | B) UNDETERMINED -- |
| | THE GREASE WASTE HAS ONLY ONE RISER. IF IT IS THE |
| | INTENT TO PROVIDE GREASE WASTE ACCESS TO ALL THREE |
| | STORE FRONTS, SHOW CONTINUATION TO ALL THREE . |
| | |
| | 2. DONE |
| | |
| | 3. DONE |
| | |
| | 4. DONE |
| | |
| | 5. DONE |
| | |
| | 6. DONE |
| | |
| | 7. DONE |
| | |
| | 8. DONE |
| | |
| | 9. DONE |
| | |
| | 10. DONE |
| | |
| | 11. DONE |
| | |
| | 12. DONE |
| | |
| | 13. DONE |
| | |
| | 14. DONE |
| | |
| | 15. DONE |
| | |
| | 16. DONE |
| | |
| | 17. DONE |
| | |
| | 18. DONE |
| | |
| | 19. NEW COMMENT - 2017 WPB AMENDS 107.3.5.1.3 - PLEASE |
| | ADD A DETAIL OF THE INTERCEPTOR INTENDED TO BE |
| | UTILIZED. EVEN THOUGH A SEPARATE PERMIT IS REQUIRED, |
| | THESE DETAILS ARE INCLUDED IN THIS REVIEW. |
| | |
| | 20. NEW COMMENT - 2020 FPC 607.1.1/613.1 - PAGE #P500 - |
| | DETAIL #5 -- ALL WATER HEATER THAT ARE NOT |
| | "RESIDENTIAL" ARE REQUIRED TO HAVE A THERMOSTATIC |
| | MIXING DEVICE INSTALLED AT THE WATER HEATER. THE |
| | THERMOSTATIC MIXING DEVICE FOR THIS REQUIREMENT SHOULD |
| | MEET THE ASSE 1017 STANDARD. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |