| Plan Review Notes For Permit 23020018 |
| Permit Number |
23020018 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-15 08:34:23 | PLAN DENIED | | | 1) PAGE M1.00 REFER TO SECTION 503.1 EXHAUST DISCHARGE. | | | EF-2 IS DISCHARGEING INTO THE GARAGE. | | | 2) PAGE M1.01 WHAT IS THE 10X8 DUCT IN THE CORRIDOR? | | | IS THAT THE AIR HANDLER OR SOME KIND OF EXHAUST. THE | | | LEGEND THE SIMBOL SAYS EXHAUST. SECTION 107 FBC | | | 3) REFER TO SECTION 402.2 VENTILATION AREA REQUIRED. | | | 2020FBC (M) FOR LIVE IN UNITS. | | | 4) PAGE M6.00 CAN'T READ THE NATURL VEMTILATION | | | CALCULATIONS FOR THE LIVE IN UNITS SECTION 107 FBC | | | 5) REFER TO SECTION 504.8.4.1 SPECIFIED LENGTH | | | AND TABLE 504.8.4.1 2020 FBC (M). CLOTHES | | | DRYER EXHAUXT DUCT. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | | | | | | | | | | |
|