| Date |
Text |
| 2023-06-02 14:31:19 | ELECTRIC REVIEW FAILED |
| | |
| | 1) GENERATOR IS STILL DETAILED ON GROUND FLOOR PLAN |
| | ALTHOUGH IT WAS REMOVED. PLEASE REMOVE ALL REFERENCES |
| | TO GENERATOR. FBC 107.2 |
| | |
| | 2) RISER DOES NOT DETAIL PANEL P, RISER INDICATES PANEL |
| | P WITH A MLO SYMBOL, RISER INDICATES PANEL P ON 5TH |
| | FLOOR, HOWEVER, PANEL P IS SHOWN TO BE LOCATED POOL |
| | EQUIPMENT RM 242, PANEL P OCP IS NOT SHOWN ON THE RISER |
| | AS BEING IN THE MDP PANEL, PANEL OPG IS DETAILED IN MDP |
| | PANEL SCHEDULE WITH 600 OCP OTHER SCHEDULES AND RISER |
| | INDICATE 400 AMP. NEC 215.5 |
| | |
| | 3) PLEASE CHANGE THE NAME IN THE SUBMITTAL FOR SHEET |
| | E7.03 FROM FIRE ALARM RISER DIAGRAM TO BUILDING |
| | ELECTRIC LOAD CALCULATIONS IN THE SUBMITTAL. |
| | |
| | 4) PLEASE PROVIDE PANEL SCHEDULES FOR PANELS EP4, WP2 |
| | ANDWP4. FBC 107.2 |
| | |
| | 5) COMPLETE MOTOR/EQUIPMENT CIRCUIT SCHEDULE TO INCLUDE |
| | PANEL ORIGIN FOR EQUIPMENT SHOWN. PLEASE REMOVE FP AS |
| | IT DOES NOT EXIST. FBC 107.2 |
| | |
| | 6) PLEASE DETAIL THAT EV CHARGING STATIONS PROVIDE ONE |
| | EV CHARGING STATION STRIPED AS AN ACCESSIBLE PARKING |
| | SPACE. ONE SUCH SPACE IS REQUIRED FOR EVERY 25 EV |
| | CHARGING STATIONS PROVIDED. SECTION 208 OF FLORIDA |
| | ACCESSIBILITY CODE REQUIRES THAT EACH TYPE OF PARKING |
| | FACILITY (SUCH AS COVERED PARKING, PARKING WITH |
| | CHARGING STATION, ETC.) MUST ALSO INCLUDE ACCESSIBLE |
| | PARKING, AND THE NUMBER OF ACCESSIBLE SPACES REQUIRED |
| | IS DETERMINED BY HOW MANY REGULAR (NON-ACCESSIBLE) |
| | PARKING SPACES OF THAT TYPE ARE PROVIDED. IF THERE ARE |
| | BETWEEN 1 - 25 PARKING SPACES PROVIDED WITH CHARGING |
| | STATIONS (I.E. PARKING FACILITY), THEN 1 SUCH SPACE |
| | MUST BE ACCESSIBLE |
| | |
| | 7) APARTMENT ELECTRIC FLOOR PLANS AND PANEL SCHEDULES |
| | DO NOT DETAIL THE REQUIRED 2 SMALL APPLIANCE CIRCUITS |
| | IN ACCORDANCE WITH NEC 21O.11(C)(1) |
| | |
| | 8) PLEASE LOCATE POOL ALL POOL EQUIPMENT, PUMP, HEATER, |
| | ETC. ON ELECTRIC FLOOR PLANS. FBC 107.2 |
| | |
| | 9) PLEASE INDICATE DISTANCE OF RECEPTACLE NEAR POOL AS |
| | BEING COMPLIANT WITH NEC 680.22(A)(1) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |