| 2023-03-01 06:27:24 | 1ST REVIEW FMC |
| | PERMIT: 23020018 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A KEY PLAN FOR THIS PROJECT INDICATING THE |
| | LOCATION OF THE PROJECT TO INDICATE THE AIR INTAKES AND |
| | EXHAUST TERMINATION LOCATIONS WILL MEET THE |
| | REQUIREMENTS OF FMC 401 INTAKES AND FMC 501 EXHAUST |
| | TERMINATION LOCATIONS. |
| | |
| | 2) ADD A NOTE ON THE MECHANICAL DRAWING STATING THAT |
| | THE GENERATOR WILL REQUIRE A SEPARATE APPLICATION WITH |
| | DOCUMENTS AND SEPARATE PLAN REVIEW AS THE GENERATOR |
| | WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 3) SHOW THAT THE PARKING GARAGE WILL MEET THE |
| | VENTILATION REQUIREMENTS OF FMC 404.1 AND PROVIDE THE |
| | DRAWING SHOWING THE DESIGN. |
| | |
| | 4) SHOW THE GARAGE EXHAUST FANS MEET THE EXHAUST |
| | DISCHARGE REQUIREMENTS OF 10 FEET FROM OPERABLE |
| | OPENINGS. FMC 501.3 EXCEPTION 2. |
| | |
| | 5) SHEET M600: THE FOLLOWING OCCUPANCY CLASSIFICATIONS |
| | SHOULD BE CALCULATED WITH THE OCCUPANT DENSITY FROM FMC |
| | 403.3.1.1 AND NOT THE ARCHITECT???S EGRESS COUNT. |
| | FITNESS, LOUNGE, CONFERENCE. ALSO SPECIFY THE FITNESS |
| | ROOM, IS IT AEROBICS OR WEIGHTS? FMC 403.3.1.1 |
| | |
| | 6) THE OCCUPANT COUNT FOR THE BREAKROOM SHOULD ALSO BE |
| | CALCULATED BY USING THE OCCUPANCY CLASSIFICATION THAT |
| | MOST RESEMBLES THE USE OF SPACE AS DETERMINED IN FMC |
| | TABLE 403.3.1.1. A BREAKROOM IS NORMALLY ASSOCIATED AS |
| | A PLACE FOR EMPLOYEES TO USE DURING A BREAK FROM WORK, |
| | AS TO RELAX, SOCIALIZE OR EAT. FMC 403.3.1.1 |
| | |
| | 7) SHEET M600: AHU-1 AND AHU-2 ARE SHOWN IN THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS. AHU???S |
| | 3A,3B,3C AND 3D ARE NOT INCLUDED IN THE MECHANICAL |
| | EQUIPMENT SIZING CALCULATIONS. PROVIDE THESE AHU???S IN |
| | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. FEC |
| | C403.2.1 |
| | |
| | 8) SHEET M1.00: EXPLAIN HOW THE GENERATOR ROOM WILL BE |
| | PROVIDED WITH MAKE UP AIR FOR THE EXHAUSTED AIR. FMC |
| | 501.4 |
| | |
| | 9) SHEET M1.00: EXPLAIN THE 48 X 22 DUCT THAT IS GOING |
| | UP TO THE COURTYARD. WHAT IS THE USE OF THIS DUCTWORK? |
| | FBC 107.3.5 |
| | |
| | 10) SHOW THE PENETRATION PROTECTION REQUIRED FOR THE 10 |
| | X 10 O/A DUCT WORK AT THE FLOOR/CEILING OF FIRST FLOOR. |
| | FMC 607 |
| | |
| | 11) SHEET M4.00: SHOW THE OUTDOOR AIR DUCTWORK FOR THE |
| | AHU???S 3C AND 3D. FMC 403.3.1.1 |
| | |
| | 12) PROVIDE THE VENTILATION METHOD, NATURAL OR |
| | MECHANICAL, FOR EACH UNIT. IF NATURAL SHOW THE |
| | CALCULATIONS, IF MECHANICAL SHOW THE DUCTWORK FOR THE |
| | OUTDOOR AIR. FMC 402 OR 403. |
| | |
| | 13) PROVIDE THE DRYER DUCT LENGTHS FOR THE UNIT DRYERS. |
| | FMC 504.8.5 |
| | |
| | 14) SHOW THE CFM???S OF EXHAUST FOR THE DRYERS AND IF |
| | NEEDED SHOW HOW THE MAKEUP AIR WILL BE BROUGHT INTO THE |
| | DRYER CLOSET. FMC 504.6 |
| | |
| | 15) ADD A NOTE STATING THAT ALL ENVIRONMENTAL AIR WILL |
| | TERMINATE A MINIMUM OF 3 FEET FROM ALL OPERABLE |
| | OPENINGS INTO THE BUILDING. FMC 501.3 EXCEPTION 3 |
| | |
| | 16) SHOW THE RETURN AIR PATH FROM THE BEDROOMS OF THE |
| | UNITS THAT HAVE A DOOR SEPARATING THE BEDROOM FROM THE |
| | LIVING SPACE. FMC 601.6 |
| | |
| | 17) SHOW THE DOORS FOR THE AHU CLOSETS WILL MEET THE |
| | RETURN AIR AND THE MATERIAL OF THE DOORS WILL MEET FMC |
| | 602.2.1 MATERIALS IN PLENUMS. |
| | |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |