| 2023-02-13 12:25:08 | ELECTRIC REVIEW FAILED |
| | |
| | 1) THERE ARE MANY CONFLICTS WITH PANEL SCHEDULE |
| | DESCRIPTION TITLE BLOCKS. EXAMPLES ARE, SCHEDULES |
| | INCORRECTLY DETAILING, MLO, MB, BUS SIZE. IN ADDITION, |
| | MANY SCHEDULES OR RISER DETAIL INCORRECT SUB PANEL |
| | BREAKER SIZES WHICH ARE IN CONFLICT WITH RISER DIAGRAM. |
| | PLEASE PROVIDE CORRECTIONS TO ALL PANEL SCHEDULES AND |
| | RISER AS APPLICABLE. |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| | AUTHORITY HAVING |
| | JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS SHALL BE |
| | PROVIDED |
| | PRIOR TO THE INSTALLATION OF THE FEEDERS. |
| | |
| | 2) PLEASE DETAIL CONDUCTOR, AND CORRECT OVERCURRENT |
| | PROTECTION SIZE FOR PANEL OPG BOTH ON RISER AND PANEL |
| | SCHEDULE. FBC 107.2 AND NEC 215.5 |
| | |
| | 3) PLEASE DETAIL OVERCURRENT PROTECTION TO PANEL OP5 |
| | FROM MPD-1 ON RISER DIAGRAM. FBC 107.2 AND NEC 215.5 |
| | |
| | 4) PLEASE DETAIL GENERATOR CONTROL CONDUIT TO FIRE PUMP |
| | CONTROLLER, EITHER BY NOTE OR PLANS TO BE INSTALLED AS |
| | PER NEC 695.14 GENERATOR CONTROL WIRING METHODS, |
| | INTEGRITY AND FIRE RATING |
| | |
| | 5) PLEASE DETAIL IN RISER DIAGRAM COMPLIANCE WITH |
| | EMERGENCY SYSTEMS, NEC 700.3 (F) TEMPORARY SOURCE OF |
| | POWER FOR MAINTENANCE OR REPAIR OF THE ALTERNATE SOURCE |
| | OF POWER. |
| | |
| | 6) PLEASE DETAIL GENERATOR SUPPLIED NATURAL GAS TO BE |
| | SUPPLIED BY ALTERNATE FUEL SOURCE AS REQUIRED PER NEC |
| | 700.12 (B)(3) DUAL SUPPLIES. PRIME MOVERS SHALL NOT BE |
| | SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR |
| | THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR |
| | COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR |
| | AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO |
| | ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED. |
| | |
| | 7) PLEASE DETAIL ALL PANIC HARDWARE FOR MAIN ELECTRIC |
| | ROOM DOORS AS REQUIRED OF NEC 110.26(C)(3) |
| | |
| | 8) PLEASE PROVIDE BY NOTE COMPLIANCE WITH NEC 408.4(B) |
| | FIELD IDENTIFICATION REQUIRED FOR SOURCE OF SUPPLY FOR |
| | SWITCH AND PANEL BOARDS |
| | |
| | 9) PLEASE PROVIDE AN ENTIRE BUILDING ELECTRIC LOAD |
| | CALCULATION. |
| | |
| | NEC 215.5 AND NEC 215.2 FEEDER CONDUCTORS SHALL HAVE AN |
| | AMPACITY NOT LESS THAN REQUIRED TO SUPPLY THE LOAD |
| | |
| | 10) PLEASE PROVIDE INFORMATION ON THE USE OF GROUND |
| | FLOOR ROOM 102 LABELED METER ROOM. FBC 107.2 |
| | |
| | 11) PLEASE CALL OUT ALL GROUNDING ELECTRODE CONDUCTOR |
| | SIZES, NOT CODE ARTICLES, AS REQUIRED BY NEC 250.66 |
| | |
| | 12) MANY APARTMENT PANEL SCHEDULES ARE MISSING ELECTRIC |
| | LOADS, IE WATER HEATERS AND AIR CONDITIONING. FBC 107.2 |
| | |
| | 13) PLEASE DETAIL ALL RECEPTACLES IN COMMON AREAS, AS |
| | APPLICABLE AND REQUIRED BY NEC 210.8 (B)(2)(KITCHENS) |
| | AS GFI PROTECTED |
| | |
| | 14) MANY CIRCUITS IN APARTMENT PANEL SCHEDULES ARE NOT |
| | DETAILED AS ARC FAULT PROTECTED, AS REQUIRED BY NEC. |
| | 210.13 PLEASE CORRECT AS APPLICABLE |
| | |
| | 15) PLEASE CORRECT LABELING ON SHEET E-400, OF ROOM |
| | DETAILED AS DOMESTIC AN FIRE PUMP ROOM AS APPLICABLE. |
| | FBC 107.2 |
| | |
| | 16) PLEASE PROVIDE A NOTE STATING, LIGHTNING |
| | PROTECTION, VOICE, DATA, SECURITY, AUDIO, VIDEO, FIRE |
| | ALARM, ACCESS CONTROL, ENERGY MANAGEMENT, GENERATOR, |
| | SIGN, SITE LIGHTING, POOL AND BDA WIRING REQUIRE |
| | SEPARATE PERMITS |
| | |
| | 17) PLEASE DETAIL ALL SMOKE/CARBON ALARMS IN ALL UNITS |
| | AS REQUIRED BY FBC R314 AND R315 |
| | |
| | 18) PLEASE DETAIL FAN TEF ON ROOF POWER PLAN. FBC 107.2 |
| | |
| | 19) PLEASE DETAIL (2) ELEVATOR CONTROLLER ON ROOF POWER |
| | PLAN. FBC 107.2 |
| | |
| | 20) PLEASE DETAIL GFI PROTECTION OF APPROPRIATE LOADS |
| | IN PANEL OF, IE DRINKING FOUNTAIN, KITCHEN AREAS |
| | |
| | 21) PLEASE DETAIL ROOF LIGHTS ON ROOF POWER PLAN. FBC |
| | 107.2 |
| | |
| | 22) PLEASE PROVIDE ALL ELECTRIC ROOM DETAILS AS ALL ARE |
| | NOT THE SAME. PLEASE INCLUDE ALL EQUIPMENT AND |
| | DIMENSIONS TO ENSURE COMPLIANCE WITH WORKING CLEARANCES |
| | AS REQUIRED BY NEC 110.26 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |