Plan Review Notes
Plan Review Notes For Permit 23011402
Permit Number 23011402
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-02 12:41:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL38754-R0 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT).
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL38754.03-R0 IS NOT RATED FOR USE IN ZONE 2 &
 3 FOR STRUCTURES LOCATED IN EXPOSURE B, C, OR D HAVE
 EITHER FLAT ROOF OR GABLE/HIP ROOF WITH MAX SLOPE OF
 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA. PROJECT LOCATED IN EXPOSURE C CATEGORY AREA.
 3. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL11602-R10 IS THE 2017 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA???S FOR THE PROPOSED
 ROOF UNDERLAYMENT SYSTEM TO BE USED. INCLUDE COVER
 PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 FOR SYSTEM USED.
 4. FBC B 107.2.1. PLEASE CLARIFY USE. SUBMITTED FLORIDA
 DBPR PRODUCT APPROVAL FL16039-R18 IS A SINGLE PLY ROOF
 SYSTEM; APPROVED COTTAGE ELEVATION PLAN A-3 SPECS A
 METAL ROOF SYSTEM.
 5. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  