Notes
Date Text
2023-03-01 10:06:22SHEET M6.1: THE OUTDOOR AIR CALCULATIONS HAVE CHANGED
 AND APPEAR TO BE LOW FOR THE OCCUPANCIES LISTED, THIS
 HAS AFFECTED THE AIR BALANCE SCHEDULE. PLEASE CORRECT
 THE AIR BALANCE SCHEDULE TO MEET THE MECHANICAL DESIGN
 FOR THIS BUILDING. FMC 508.1.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  