Plan Review Notes
Plan Review Notes For Permit 23011356
Permit Number 23011356
Review Stop M
Sequence Number 1
Notes
Date Text
2023-02-06 11:14:151ST REVIEW FMC
 PERMIT: 23011356
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 NOT ENOUGH INFORMATION SUBMITTED TO COMPLETE A
 MECHANICAL PLAN REVIEW OF THE GREASE HOOD DESIGN AT
 THIS TIME.
 THE ITEMS LISTED BELOW ARE ONLY A PARTIAL LIST OF
 HELPFUL INFORMATION AND IN NO WAY SHOULD THEY BE TAKEN
 AS A COMPLETE REVIEW.
  
 1) PROVIDE A COMPLETE DESIGN FOR THIS HOOD INCLUDING
 THE HOOD TYPE, AND SIZE. SHOW THAT THE GREASE HOOD WILL
 MEET CLEARANCES TO COMBUSTIBLES. GREASE DUCT MATERIAL,
 SIZE AND TERMINATION DETAILS. FBC 107.3.5
  
 2) SHOW THAT THE GREASE DUCT WILL MEET THE REQUIRED
 CLEARANCE TO COMBUSTIBLES. FMC 506
  
 3) PROVIDE THE EQUIPMENT DETAILS FOR THE EQUIPMENT THAT
 IS TO BE USED UNDER THIS HOOD. FMC 507.1
  
 4) THE AIR VELOCITY OF THE GREASE DUCT MUST MEET THE
 MINIMUM REQUIREMENT IN FMC 506.3.4
  
 5) SHOW THAT THE HOOD EXHAUST OPERATION WILL MEET THE
 REQUIREMENTS IN FMC 507.1.1
  
 6) THE SUBMITTED M2.1 AND M6.1 SHEETS HAVE CHANGED FROM
 THE APPROVED DRAWINGS. THESE SHEETS SHOULD BE SUBMITTED
 AS REVISIONS TO THE APPROVED SET OF DRAWINGS.
  
 7) SHOW THAT THE HOOD WILL MEET THE CLEARANCE TO
 COMBUSTIBLES REQUIREMENTS OF FMC 507.2.6
  
 8) SHEET M2.1 REFERENCES THE KEF AS AN INLINE BY
 GREENHECK QEI-12 BUT IT IS NOT INCLUDED ON THE M6.1
 SCHEDULES. PROVIDE THE INFORMATION FOR THE KEF
 INCLUDING THE DETAILS FOR HOW TO ENCLOSE THIS INLINE
 FAN. FMC 506.5.1.2
  
 9) SHEET M2.1: THE KSF IS LABELED AS GREENHECK SQ-120-
 VG BUT IS NOT SHOWN ON THE SCHEDULES SHEET. PROVIDE
 THIS INFORMATION ON THE SCHEDULE SHEET. FBC 107.3.5
  
 10) SHOW THAT THE MAKE UP AIR OPERATION WILL MEET THE
 REQUIREMENTS OF FMC 508.1
  
 11) SHEET M2.1: PROVIDE THE INFORMATION FOR THE LOUVERS
 OF BOTH THE EXHAUST AND INTAKE ON THE SCHEDULE SHEET.
 ALSO PROVIDE NOA???S FOR THESE LOUVERS. FBC 107.3.5
  
 12) PROVIDE A DETAIL DRAWING OF THE GREASE DUCT
 INCLUDING SIZES AND CLEANOUTS. FMC 506.3.8
  
 13) PROVIDE A SITE PLAN SHOWING THE GREASE DUCT
 TERMINATION LOCATION WILL MEET THE TERMINATION
 REQUIREMENTS OF FMC 506.3.13.2 AND 506.3.13.3
  
 14) PROVIDE A SITE PLAN SHOWING THE MAKEUP AIR INTAKE
 TERMINATION LOCATION MEETS THE REQUIREMENTS OF FMC
 401.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  