Plan Review Notes
Plan Review Notes For Permit 23011348
Permit Number 23011348
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-02 18:57:40RESIDENTIAL (R2)BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23011348
 2000 PRESIDENTIAL WAY 2005
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- PROVIDE SITE SPECIFIC SIGNED AND SEALED WIND LOAD
 CALCULATIONS FOR SLIDING GLASS DOORS. SEC. 107.2.1.2
 CITY AMENDMENTS AND SEC. 1609.1 FBC-BUILDING.
  
 2- FBC-B 1405.4, A FLASHING DETAIL OR SPECIFICATION IS
 REQUIRED. THIS COMMENT CAN BE RESOLVED BY DOING ONE OF
 THE FOLLOWING:
 REVISE THE FLOOR PLAN TO NOTE THAT FLASHING IS REQUIRED
 AND NOTE THE CODE REFERENCE - EXAMPLE "FLASHING IN
 ACCORDANCE WITH FBC R 703.4/B 1405.4 WILL BE
 INSTALLED".
  
 PROVIDE A WRITTEN SPECIFICATION IN LETTER FORM - THIS
 MAY INCLUDE MORE THAN ONE OPTION
  
 PROVIDE A FLASHING DETAIL - THIS MAY INCLUDE MORE THAN
 ONE OPTION
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  