| 2023-02-01 10:42:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET A 1.0 - THERE IS AN INDICATION OF AN OCCUPANCY |
| | LOAD CALCULATION OF 2084 SQ FT @ 60 SQ FT PER PERSON, |
| | HOWEVER, THE FLOOR PLAN DOES NOT DELINEATE TO 2084 SQ |
| | FT. |
| | |
| | PER NFPA 101 CH 7 MEANS OF EGRESS |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING |
| | OR PORTION THEREOF SHALL BE NOT LESS THAN THE NUMBER OF |
| | PERSONS DETERMINED |
| | BY DIVIDING THE FLOOR AREA ASSIGNED TO THAT USE BY THE |
| | OCCUPANT |
| | LOAD FACTOR FOR THAT USE AS SPECIFIED IN TABLE 7.3.1.2, |
| | FIGURE 7.3.1.2(A), |
| | AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND NET AREA |
| | FIGURES ARE GIVEN |
| | FOR THE SAME OCCUPANCY, CALCULATIONS SHALL BE MADE BY |
| | APPLYING THE |
| | GROSS AREA FIGURE TO THE GROSS AREA OF THE PORTION OF |
| | THE BUILDING DEVOTED |
| | TO THE USE FOR WHICH THE GROSS AREA FIGURE IS SPECIFIED |
| | AND BY APPLYING |
| | THE NET AREA FIGURE TO THE NET AREA OF THE PORTION OF |
| | THE BUILDING DEVOTED |
| | TO THE USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED |
| | |
| | PLEASE REVIEW AND BETTER DEFINE THE AREA OF 2084 IN |
| | RELATIONS TO ALL OTHER AREAS THAT WOULD MEET THE |
| | REQUIRMENTS AND 58 PEOPLE AS PROPSED. |
| | |
| | |
| | |
| | 2) SHEET A 1.0 - THERE ARE NO INDICATIONS OF EXIT DOOR |
| | HARDWARE NOR A DOOR SCHEDULE THAT INDICATES COMPLIANCE |
| | WITH NFPA 101, INCLUDING LOCKS & LATCHES. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE |
| | PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF OPERATION |
| | AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS. |
| | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| | SHALL BE LOCATED AS |
| | FOLLOWS: |
| | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| | FLOOR FOR OTHER |
| | THAN EXISTING INSTALLATIONS |
| | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| | FLOOR |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF WITH NOT |
| | MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE |
| | SPECIFIED IN |
| | 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR |
| | 7.2.1.5.10.7 |
| | |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS MEETING THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |