| Date |
Text |
| 2023-03-02 14:38:06 | ELECTRIC REVIEW FAILED |
| | |
| | 1) ELECTRIC RISER DIAGRAM DOES NOT INCLUDE ALL |
| | EQUIPMENT. PLAN INDICATES A NEW PANEL B AND EXISTING |
| | PANEL A AND NO PANELS LABELED AS D. PLEASE DETAIL ON |
| | ELECTRIC RISER DIAGRAM ALL EQUIPMENT, CONDUIT, |
| | CONDUCTORS, OVERCURRENT PROTECTION AND GROUNDING |
| | ELECTRODE SYSTEM AS REQUIRED PER NEC 215.5 |
| | |
| | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| | THE FEEDERS. |
| | |
| | 2) PANEL SCHEDULES DETAIL ALL AIR CONDITIONING |
| | EQUIPMENT AS FUTURE, HOWEVER, CIRCUIT WIRING IS |
| | INDICATED ON FLOOR PLAN. IF HVAC EQUIPMENT IS TO BE |
| | INSTALLED PLEASE INDICATE EQUIPMENT ON FLOOR PLANS AND |
| | PROVIDE SPECIFICATIONS. FBC 107.2 |
| | |
| | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | 3) PANEL SCHEDULES INDICATE A WATER HEATER, HOWEVER, |
| | NONE IS DETAILED ON FLOOR PLAN. PLEASE PROVIDE DETAILS |
| | ON FLOOR PLAN AND PROVIDE SPECIFICATIONS. FBC 107.2 |
| | |
| | 4) PLEASE PROVIDE A LETTER FROM FPL DETAILING AVAILABLE |
| | FAULT CURRENT AS INDICATED ON ELECTRICAL PLANS. FBC |
| | 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |